22
MSC4000 - MSC15000 USER GUIDE
H9 Suction Pressure
Actual:
0 psi
Offset
[0 psi]
Fullscale
600 psi
H10 Suction Pressure
Actual:
0 psi
Offset
0 psi
Fullscale
[600 psi]
H11 Flow
Actual:
OPEN
Offset
[0 scfm]
Fullscale
100 scfm
H12 Flow
Actual:
OPEN
Offset
0 scfm
Fullscale
[100 scfm]
H13 AUX #1
Actual:
OPEN
Offset
[0]
Fullscale
100
H14 AUX #1
Actual:
OPEN
Offset
0
Fullscale
[100]
H15 AUX #2
Actual:
OPEN
Offset
[0]
Fullscale
100
H16 AUX #2
Actual:
OPEN
Offset
0
Fullscale
[100]
E4 DRAIN SETUP MENU
Press SET to Select
I1 Drain #1
Type
[DEMAND]
Interval (m:s)
10:00
Duration
2 Sec
System Drains - (E & I Series Menus) - Each of the two (2) drain controls can be programmed to be either a
‘TIMED’ or ‘DEMAND’ drains.
•
If Timed is selected, the drain will activate to the “Interval” time setting for the period of time indicated in the
‘Duration’ time setting
•
If DEMAND is selected, the drain will operate for the period of time indicated in the ‘Duration’ time setting, when
a drain input signal is sensed from the demand drain float. A DRAIN FAULT Alarm can occur if float does not
respond as expected. When a fault is detected, the drain solenoid will be ‘pulsed’ for ten minutes in attempt to
clear the faulted drain.
•
The ‘Auto Test’ feature will operate the drain for the period of time indicated in the Duration setting at the
specified Interval. This feature is intended to prevent sediment buildup by activating the drain periodically and
‘blowing out’ any possible debris.
Содержание Airtek MSC Series
Страница 1: ...MSC Refrigerated Air Dryer User Guide Models MSC4000 to MSC15000...
Страница 9: ...9 MSC4000 MSC15000 USER GUIDE 4 4 Start Up Checklist...
Страница 45: ...45 MSC4000 MSC15000 USER GUIDE 11 Warranty and Product Registration...
Страница 46: ...46 MSC4000 MSC15000 USER GUIDE 12 Drawings Spare Parts...