Refrigerating Specialties Division

2

Adjustment

Install an accurate pressure gauge in the gauge port. Back the
adjusting stem all the way out to stop. This will reduce the set point to
its lowest level and cause the valve to open wide. Start the system,
and when suction pressure is about the desired pressure, turn the
adjusting stem in until the pressure gauge shows a slight rise in the
inlet pressure. At this point the adjusting stem may be turned in
(clockwise) to raise the pressure further, or backed out (counter-
clockwise) to lower it; but the final adjustment should be made after
the system has been operating for a period of time.

INLET PRESSURE SETTING RANGES

Approx. Pressure Change

Factory Set Point

Set Point Ranges

per Turn of

(unless otherwise

Adjusting Screw

specified)

A: 0 to 10.3 bar

1 .7 bar (25 psi)

2.8 bar (40 psig)

(0 to 150 psig)

V:

500mm hg to 8.3 bar

1.7 bar (25 psi)

1 . 0 bar (15 psig)

(20 in hg to 120 psig)

D: 5.2 to 19.3 bar

3.7 bar (53 psi)

9.7 bar (140 psig)

(75 to 280 psig)

Type A4AZ (See Figs 1 and 2)

Description

The A4AZ Inlet Pressure Regulator is the basic building block from
which most Series A4 variations are made. This regulator incorporates
the specially designed Modudapter

®

 to accommodate the

Adaptomode

®

 bolt on modules, providing unique modular construction

and many control valve variations with the use of a few modules and
kits. See page 3 for an explanation of "Basic Adaptomode Functions",
describing modules, module placement and schematic pilot circuit
flow diagrams for all variations covered within this bulletin.

The A4AZ regulator is a complete factory assembled and bench tested
valve and, in itself, may be used as a basic inlet pressure regulator. In
addition, this valve can easily be modified in the field to perform the
function of the A4AS, A4AB or A4AD valve variations.

Type A4AS (See Fig. 3)

Description

The Type A4AS is an inlet pressure regulator with a pilot electric shut
off. The integrally mounted solenoid must be energized for the valve
to function as a regulator. When de-energized the regulator is closed
regardless of inlet pressure.

Purpose

The Type A4AS should be used whenever it is required to stop all flow
(in the normal fluid flow direction) through the regulator. This could
include use in defrost applications as well as part of a temperature
control system.

Principles of Operation

The operation of the A4AS is the same as that described on page 1,
except the inlet pressure from passage N must pass through the S6A
Pilot Solenoid Valve before it can reach the diaphragm. Thus the S6A
Pilot Solenoid must be energized before the A4AS can begin to regulate
regardless of inlet pressure.

Adjustment

With the solenoid pilot electrically energized, proceed as described
above.

Type A4AB (See Fig. 4)

Description

The Type A4AB is an Inlet Pressure Regulator with a Pilot Electric
Wide-opening, or Bypass, variation. When the integrally mounted
solenoid is energized the main valve is wide open, thereby bypassing
the regulator function i.e. not regulating. However, in the wide open

mode the regulator will still require the 0.14 bar (2 psi) minimum
pressure drop. When the solenoid is de-energized the valve functions
as an Inlet Pressure Regulator.

Purpose

The Type A4AB frequently is used with the wide-open function where
maximum refrigeration capacity from an evaporator is required. During
the defrost of the evaporator, the regulator pilot solenoid is de-
energized thus functioning as a defrost relief regulator or for high
pressure limit protection.

When used in a discharge pressure line, it can when de-energized,
hold back enough pressure for some heat reclaim or defrosting function
and then, when energized, allow the discharge pressure to drop to a
lower level. Frequently this regulator is used in the wide open mode
for evaporator pump out prior to hot gas defrost.

Principles of Operation

The operation of the A4AB is the same as that described on page 1
when operating as a regulator (Pilot Solenoid de-energized). When
the solenoid is energized the upstream pressure from passage N
bypasses the underside of the diaphragm and is fed directly to the top
of the piston where, provided a 0.14 bar (2 psi) pressure difference
exists across the main valve, the Modulating Plug will be held wide
open.

Adjustment

With the solenoid pilot electrically de-energized, proceed as described
above.

Type A4AD (See Fig. 5)

Description

The Type A4AD is a Dual Inlet Pressure Regulator capable of regulating
at two different pressure set-points. When the integrally mounted S6A
Pilot Solenoid Valve is energized the regulator is controlling at the
lower of two set-points, which must be adjusted on the pressure pilot
over the center of the main valve. When the solenoid is de-energized
the regulator is controlling at the higher set-point, which must be
adjusted on the bolt-on (outboard) pressure pilot.

Purpose

The Type A4AD uses are similar to those for the A4AB except, instead
of operating in a wide-open position when the pilot solenoid is
energized, the regulator Is controlling at some preset level.

Typical uses include capacity control of an evaporator at two different
pressure levels to regulate temperature, and evaporator pressure
control combined with defrost pressure relief.

Principles of Operation

The operation of the A4AD is similar to that described on page 1.
When the Pilot Solenoid is energized, upstream pressure from passage
N is made available to both diaphragms. Since the path of least
resistance will be through the Pressure Pilot with the lower set-point
(lower range spring force) that pilot will control.

When the Pilot Solenoid Is de-energized, upstream pressure from
passage N can flow only to the high pressure pilot, which will then
control the regulator.

Adjustment

Electrically de-energize the solenoid pilot and adjust the modular
(bolt-on) pressure pilot for the desired high pressure setting following
the adjusting procedure as described above. Energize the solenoid
pilot and adjust the integral pressure pilot for the desired low pressure
setting following the adjusting procedure described above.

Содержание ADAPTOMODE A4AS-DN

Страница 1: ... C 50 F to 220 F Principles of Operation See Fig 1 The inlet pressure enters the space under the diaphragm through passage N When the force created by the pressure exceeds the force of the range spring the diaphragm is lifted off the pilot seat allowing pressure to enter on top of the power piston This causes the power piston to move downward forcing the modulating plug to open and modulate to mai...

Страница 2: ...ng the regulator function i e not regulating However in the wide open mode the regulator will still require the 0 14 bar 2 psi minimum pressure drop When the solenoid is de energized the valve functions as an Inlet Pressure Regulator Purpose The Type A4AB frequently is used with the wide open function where maximum refrigeration capacity from an evaporator is required During the defrost of the eva...

Страница 3: ...Refrigerating Specialties Division 3 BASIC ADAPTOMODE FUNCTIONS Fig 2 A4AZ Fig 3 A4AS Fig 4 A4AB Fig 5 A4AD ...

Страница 4: ...4A Regulators General Procedure The construction of the regulator and the method of disassembly are relatively simple but some procedures must be followed to avoid damage The following describes the procedure for the basic A4A special instructions for other types are included in other appropriate sections Disassembly Take care when removing Seal Caps 1 and 44 in case some refrigerant may be trappe...

Страница 5: ...e Port Pipe Plug 28 Adapter Body 29 Gasket Body 30 Piston Stem 31 Screw Body 32 Body 33 Throttling Plug Asm 34 Spring Closing 35 Dirt Wiper Retainer 36 Dirt Wiper 37 Seal Bottom Cap 38 Bottom Cap 39 Screw Bottom Cap 40 Packing Washer 41 Packing Ring 42 Stuffing Box Nut 43 Gasket Seal Cap 44 Seal Cap 45 Gasket Flange 46 Bolt Flange 47 Nut Flange 48 Pilot Body 49 Screw Pilot Body 50 O Ring 51 Moduda...

Страница 6: ...odular Solenoid Pilot Figs 10 and 12 This solenoid pilot may be mounted on either Pad 1 or 2 depending on the function desired see pages 2 and 3 Before working on any Fig 11 A2D2 A2D MODULAR PRESSURE PILOT A2D2 Port Sizes 20 50mm 3 4 2 A2D Port Sizes 65 100mm 2 4 1 2 3 4 5 6 11 8 9 10 12 13 14 15 16 17 18 19 48 49 50 solenoid pilot make sure the coil is de energized and will remain so during the s...

Страница 7: ...1 440 60 Yellow Red leads 0 39 0 13 1 115 50 Yellow Blue leads 1 22 0 21 1 230 50 Yellow leads 0 65 0 26 1 Other Contact Factory On transformer coil the 6 volt leads are always black Fig 12 S6A MODULAR SOLENOID PILOT A2D MODULAR PRESSURE PILOT MODUPLATE Safe Operation See also Bulletin RSBCV People doing any work on a refrigeration system must be qualified and completely familiar with the system a...

Страница 8: ...It Range D make sure has 2 open ruptured or badly deformed diaphragms Diaphragm follower stuck damaged or frozen Clean or replace Install follower carefully A4AS A4AB Modular Solenoid Pressure drop across valve too high over 21 bar 300 psig Lower pressure Pilot not opening drop Improper power supply Correct Replace solenoid coil Piston worn too much clearance Replace piston Check for reason If use...

Страница 9: ...Flange Pipe Size Socket I D Neck O D Number 2 Pkg O D I D Flge Pkg Pipe Size Pkg No Socket Weld No 2 Pkg mm Inches Inches 2 Pkg Inches NW No Inches mm Inches mm Weld Neck Inches mm Inches mm 20 3 4 3 4 200016 3 4 20 1 070 27 81 1 050 26 67 200020 200023 1 1 8 28 57 1 130 28 70 200027 and and 1 200017 1 25 1 365 34 67 1 315 33 40 200021 200024 1 3 8 34 92 1 380 33 05 200028 25 1 1 1 4 200018 1 1 4 ...

Страница 10: ...G 40 3 42 4 1 61 L ADAPTER 2 A4A DN DUCTILE IRON GGG 40 3 COVER BOTTOM A4A S4A 1 5 8 to 2 1 2 DUCTILE IRON GGG 40 3 BONNET A4W DUCTILE IRON GGG 40 3 COMPONENT DESCRIPTION MATERIAL Kv VOLUME BODY 2 1 2 A4A DN DUCTILE IRON GGG 40 3 60 3 19 L ADAPTER 3 A4A DN DUCTILE IRON GGG 40 3 COVER BOTTOM 3 A4A S4A DUCTILE IRON GGG 40 3 BONNET A4W DUCTILE IRON GGG 40 3 COMPONENT DESCRIPTION MATERIAL Kv VOLUME BO...

Отзывы: