9
Mounting Guidelines
The ACR7000 drive/controllers are vented products. To prevent material spilling into the drive, mount it under an
overhang or in a suitable enclosure.
ACR7000 products are made available under “Restricted Distribution” for use in the “Second Environment” as
described in the publication EN 61800-3 ed2.0.
Cable Routing
Route high power cables (motor and mains) at right angles to low power cables (communications and
inputs/outputs). Never route high and low power cables parallel to each other.
Panel Routing
The minimum clearance between products is 0.62 inches (15.75mm). The minimum clearance above and below a
drive is 1 inch (25.4 mm).