![Parker AC30 series Скачать руководство пользователя страница 24](http://html.mh-extra.com/html/parker/ac30-series/ac30-series_product-manual_755681024.webp)
18
AC30 series General Purpose I/O Option
Specification
Contact form (each relay)
1 pole normally open
Contact rating
3A @ 250V AC
3A @ 30V DC
Overvoltage category
Category II, TN supply.
Minimum switching capacity
100µA, 100mVDC
Recommended load
Resistive
Contact suppression
None. External components must be
added to protect the relay contacts
against inductive or capacitive loads.
Expected life
300 x 10
3
operations (Electrical)
20 x 10
6
operations (Mechanical)
Example application
Relay Output RLY11 to 230VAC Load:
~
230V AC
Note: the load must be
earthed, if necessary, for
safety.
LOAD
X23/02
X23/01