AC30 EtherNet IP Option 

Configuration 

The option requires configuration of the device address and mapping 
of the process data to the master.  The Producer Assembly instance 
number and Consumer Assembly instance number may be changed 
from the defaults if required.  Note that some communication 
parameters only become active after the AC30 leaves the 
configuration state. 

 

The 

0044

 

Comms Required

 parameter must be set to 

ETHERNET 

IP

.  

 

Address 

There are three methods to set the IP address, subnet mask and 
gateway address of the device: the slave sets its own address, the 
address is set externally, say be a PLC, or the address is set by a 
DHCP server.   The parameter 

0199 Address Assignment

 is used to 

choose the method. 

 

If the IP address is set by the slave (

Address Assignment = FIXED

then three further parameters must be set.  These are: 

0200 Fixed IP Address 

0201 Fixed Subnet Mask 

0202 Fixed Gateway Address 

 

Producing / Consuming Instance Numbers                                                                                                      

The Producing Instance Number may be changed from its default of 
0064h if required using the parameter 

0226 ENET Producing Inst

  

The Consuming Instance Number may be changed from its default of 
0096h if required using the parameter 

0227 ENET Consuming Inst

  

The Configuration Instance Number is fixed as 0005h. 

 

Process Data 

The cyclic I/O data is configured by using the read and write process 
data mapping tables in the AC30.  These tables are two parameter 
arrays in which AC30 parameter numbers may be added.  

At least one AC30 parameter must be mapped to the process data.  
String-type parameters may not be mapped. 

 

Read Mapping 

The read process data represents cyclic data sent from the PLC to the 
AC30.  Only writable AC30 parameters, that are not configuration 
parameters, may be added to the read process data. 

 

Содержание AC30 series

Страница 1: ...s EtherNet IP Option HA501842U001 Issue 2 Technical Manual aerospace climate control electromechanical filtration fluid gas handling hydraulics pneumatics process control sealing shielding ENGINEERING...

Страница 2: ......

Страница 3: ...en to ensure the accuracy of this document it may be necessary without notice to make amendments or correct omissions Parker cannot accept responsibility for damage injury or expenses resulting theref...

Страница 4: ...lyze all aspects of the application follow applicable industry standards and follow the information concerning the product in the current product catalog and in any other materials provided from Parke...

Страница 5: ...ablished safety practices with the installation process operation and maintenance of this equipment and with all the hazards involved Product Warnings DANGER Risk of electric shock WARNING Hot surface...

Страница 6: ...re is conflict between EMC and Safety requirements personnel safety shall always take precedence Never perform high voltage resistance checks on the wiring without first disconnecting the drive from t...

Страница 7: ...istributors and in accordance with EU directive 2002 96 EC undertakes to withdraw and dispose of its products fully respecting environmental considerations For more information about how to recycle yo...

Страница 8: ...ted CIP Objects 8 Example Configuration 9 Configuration Summary 9 Example Using Allen Bradley RSLogix 5000 10 Configuring the AC30 13 Acyclic Data Exchange 15 Overview 15 Arrays 17 Strings 17 Lost Com...

Страница 9: ...Appendix A Array Parameter Numbers 35 Array Example 35 Appendix B Data Types 36...

Страница 10: ...Ethernet interface Device Level Ring DLR and linear network topology supported Network Status and Module Status LEDs Up to 256 bytes of consumed data and 256 bytes of produced data CIP Parameter Obje...

Страница 11: ...C30 EtherNet IP Option Installation 1 Remove the Graphical Keypad GKP by pulling from the top down and remove 2 After removing the screw slide the control module lower cover down slightly and then rem...

Страница 12: ...3 AC30 EtherNet IP Option 3 Click the Option into place and tighten the retaining screw as shown 4 Slide and click back the control module lower cover tighten the retaining screw and slot back the GKP...

Страница 13: ...ckets may be used Having 2 ports reduces the need for additional Ethernet switches The socket shields are connected to protective earth via a filter Cable Type CAT5E or CAT6 cable up to 100m between n...

Страница 14: ...flashing On line no connections established Red Duplicate IP address or fatal error Red flashing One or more connections timed out CIP Class 1 or 3 Module Status MS LED State Indication Off No power G...

Страница 15: ...XED then three further parameters must be set These are 0200 Fixed IP Address 0201 Fixed Subnet Mask 0202 Fixed Gateway Address Producing Consuming Instance Numbers The Producing Instance Number may b...

Страница 16: ...mber See the Appendix A Array Parameter Numbers Default Mapping The process data mapping will contain a factory default mapping The default mapping may be overwritten if required Cyclic Data Exchange...

Страница 17: ...following CIP objects are supported Identity Object 01h Message Router 02h Assembly Object 04h Connection Manager 06h Parameter Object 0Fh DLR Object 47h QoS Object 48h Vendor Specific Object A2h Port...

Страница 18: ...s IP Address Subnet Mask Gateway Address Read Process Mapping Table Data Type Bytes 000 0627 Comms Control Word WORD 2 001 0681 Comms Reference REAL 4 002 000 003 000 Write Process Mapping Table Data...

Страница 19: ...assumed The following is an example of configuring the PLC 1 Start a new project and select the required PLC processor and chassis type In this example a 1756 L55 processor and 1756 A7 rack is chosen...

Страница 20: ...AC30 EtherNet IP Option Enter the name and IP address of the Ethernet interface 3 Insert the device Right click on the Ethernet Interface module and select New Module Select the Generic Ethernet Modu...

Страница 21: ...either direction to match the configuration of the AC30 in this example 4 Save and Download When completed with the setup the project may be saved and downloaded to the PLC For testing the data can be...

Страница 22: ...meter 0044 Comms required must be set to Ethernet IP In the Application tab the following settings are available in the Communications block Select the method to set the IP address subnet mask and gat...

Страница 23: ...parameters to the Read Process Mapping table parameter 0055 Read Mapping by selecting them from the popup window Add the required parameters to the Write Process Mapping table parameter 0120 Write Map...

Страница 24: ...AC30 parameter number The supported services are Get Attribute Single and Set Attribute Single The instance attributes are summarized as Attribute Name Access Type Description 1 Name Get SHORT_STRING...

Страница 25: ...Value Not supported The Data Type Code can be found Appendix B Data Types The class attributes are summarized as Attribute Name Access Type Description 1 Revision Get UINT Object revision 0001h 2 Max...

Страница 26: ...the parameter number that represents a single element will allow access only to that element See Appendix A Array Parameter Numbers Strings String parameters may be accessed via its parameter number...

Страница 27: ...en opened towards the device Comms Break Trip The Comms Break trip will generate a trip if a break in communications is detected A trip event will be generated when a transition from TRUE to FALSE of...

Страница 28: ...edge signal from FALSE to TRUE will create a diagnostic event The Comms Event Clear parameter must be set FALSE 0188 Comms Event Clear A rising edge signal from FALSE to TRUE will remove a diagnostic...

Страница 29: ...es a link to the Network Interface pages and the Parameter Data pages Network Interface Pages The Network Interface page provides basic information about the option The Network Configuration page allo...

Страница 30: ...ected from web access by placing a file called web_accs cfg in the directory to protect see the FTP Server section All the built in web files are virtual files and are located in the root directory Th...

Страница 31: ...files are stored on the file system the built in web files are virtual files User Accounts User accounts are stored in the configuration file ftp cfg This file holds the usernames passwords and home d...

Страница 32: ...THERCAT 9 ETHERNET IP 10 MODBUS RTU 11 MODBUS TCP 12 PROFIBUS DPV1 13 PROFINET IO Default NONE Communications option parameter Sets the required communications option 0199 Address Assignment Range RW...

Страница 33: ...RW Saved Config Type DWORD IP address 0 0 0 0 255 255 255 255 Default 0 0 0 0 Communications option parameter Subnet mask to be set by the slave The parameter Address Assignment must be set to SLAVE S...

Страница 34: ...option parameter Allows access to the parameter page via the option s web server 0205 Option FTP Enable Range RW Saved Config Type BOOL FALSE TRUE Default TRUE Communications option parameter Allows...

Страница 35: ...onfig Type Array of UINT 0 Last parameter number Default Communications option parameter Sets the required read process data mapping Each entry in the table represents the required parameter number 01...

Страница 36: ...trip 0226 ENet Producing Inst Range RW Saved Config Type WORD 0x0000 0xFFFF Default 0064 EtherNet IP communications option parameter Sets the Producing Instance Number for EtherNet IP 0227 ENet Consu...

Страница 37: ...BOOL FALSE TRUE Default FALSE Communications option parameter A rising edge FALSE to TRUE will create a diagnostic event 0188 Comms Event Clear Range RW Saved Config Type BOOL FALSE TRUE Default FALS...

Страница 38: ...ption fitted 0046 Comms State Range Type USINT enumerated 0 SETUP setup in progress 1 NW INIT network related initialisation tasks are being performed 2 WAIT PROCESS the module will stay in this state...

Страница 39: ...rror or duplicate IP address detected 6 RESERVED 7 EXCEPTION major fault 8 NONE option not fitted Ethernet IP communications option parameter Indicates the state of the communications option fitted as...

Страница 40: ...address 0 0 0 0 255 255 255 255 Communications option parameter Indicates the gateway address of the slave 0198 Option DHCP Enabled Range Type BOOL FALSE TRUE Communications option parameter Indicates...

Страница 41: ...ter Serial number of the option communications module 0051 Comms Diagnostic Range Type USINT enumerated 0 NONE 1 HARDWARE MISMATCH required communications option does not match that fitted or no optio...

Страница 42: ...TE 0x00 0xFF Communications option parameter Exception code associated with the Diagnostic parameter being in EXCEPTION 0054 Comms Net Exception Range Type BYTE 0x00 0xFF Communications option paramet...

Страница 43: ...l fitted option No option is fitted but one is required Invalid Configuration Diagnostic INVALID CONFIGURATION Invalid read or write process data mapping No read or write process data mapped Invalid c...

Страница 44: ...eter array called My Array has 4 elements Parameter Number Parameter My Array 0152 Whole array 0153 index 0 0154 index 1 0155 index 2 0156 index 3 If the parameter number of the whole array is 0152 th...

Страница 45: ...UDINT 4 DATE Date UDINT 4 TIME_OF_DAY Time of day UDINT 4 DATE_AND_TIME Date and time of day UDINT 4 STRING String SHORT_STRING n BYTE Bit string length 8 USINT 1 WORD Bit string length 16 UINT 2 DWO...

Страница 46: ...y parker com IE Ireland Dublin Tel 353 0 1 466 6370 parker ireland parker com IN India Mumbai Tel 91 22 6513 7081 85 IT Italy Corsico MI Tel 39 02 45 19 21 parker italy parker com JP Japan Tokyo Tel 8...

Отзывы: