AC30 EtherNet IP Option
Configuration
The option requires configuration of the device address and mapping
of the process data to the master. The Producer Assembly instance
number and Consumer Assembly instance number may be changed
from the defaults if required. Note that some communication
parameters only become active after the AC30 leaves the
configuration state.
The
0044
Comms Required
parameter must be set to
ETHERNET
IP
.
Address
There are three methods to set the IP address, subnet mask and
gateway address of the device: the slave sets its own address, the
address is set externally, say be a PLC, or the address is set by a
DHCP server. The parameter
0199 Address Assignment
is used to
choose the method.
If the IP address is set by the slave (
Address Assignment = FIXED
)
then three further parameters must be set. These are:
0200 Fixed IP Address
0201 Fixed Subnet Mask
0202 Fixed Gateway Address
Producing / Consuming Instance Numbers
The Producing Instance Number may be changed from its default of
0064h if required using the parameter
0226 ENET Producing Inst
The Consuming Instance Number may be changed from its default of
0096h if required using the parameter
0227 ENET Consuming Inst
The Configuration Instance Number is fixed as 0005h.
Process Data
The cyclic I/O data is configured by using the read and write process
data mapping tables in the AC30. These tables are two parameter
arrays in which AC30 parameter numbers may be added.
At least one AC30 parameter must be mapped to the process data.
String-type parameters may not be mapped.
Read Mapping
The read process data represents cyclic data sent from the PLC to the
AC30. Only writable AC30 parameters, that are not configuration
parameters, may be added to the read process data.