25
6053/6055 Modbus Plus Communications Interface
Appendix C External Control of the Drive
590+
REM. SEQUENCE
Tag 536, Default = 0x0000
Reserved bits are undefined when read and should be set Zero when written.
Bit Number
Mask
Name
Comment
0 (lsb)
0x0001
Remote Enable
1 0x0002
Remote
Start
2 0x0004
Remote
Jog
3
0x0008
Remote Jog Mode
Selects Jog Speed
4 0x0010
Reserved
5 0x0020
Reserved
6 0x0040
Reserved
7 0x0080
Reserved
8
0x0100
Remote Alarm Ack
Alarm Acknowledge
9
0x0200
Remote/Remote Trip
Remote Trip (High for OK)
10 0x0400
Reserved
11 0x0800
Reserved
12 0x1000
Reserved
13 0x2000
Reserved
14 0x4000
Reserved
15
0x8000
Reserved
Useful Commands using EI-ASCII - REM. SEQUENCE
Tag 536, Default = 0x0C07
/Remote
Trip
Alarm
Ack
Jog
Mode
Jog Start
Enable Command
Start Drive
1
0
X
0
1
1
0x0203
Stop Drive
1
0
X
0
0
1
0x0201
Disable Drive
1
0
X
X
X
0
0x0200
Jog Setpoint 1 1
0
0
1
0
1
0x0205
Jog Setpoint 2 1
0
1
1
0
1
0x020C
Remote Trip
0
0
X
X
X
X
0x0000
Reset Alarm a) 1
1
0
0
0
0
0x0300
Reset Alarm b)
Healthy
Output
Bit 11
Reset Alarm c) 1
0
50
0
0
0
0x0200