Refrigerant Leak Detector  

023-064X Technical Manual  

Document No.70-PHW-1018-R3.2 

MTA V8.5 

 

© 1997-2020 No part of this publication may be 
reproduced,  stored  in  a  retrieval  system,  or 
transmitted,  in  any  form  or  by  any  means, 
electronic,  mechanical,  photocopying,  recording, 

or  otherwise,  without  the  prior  written 
permission of Parker Hannifin Canada.   
 
Micro  Thermo  Technologies  is  a  trademark  of 

Parker  Hannifin  Canada.    All  rights  reserved 
worldwide. 

 

 
 
 
 
 
 
 
 

 

 
 

 

Micro Thermo Technologies, 12855 rue Brault, Mirabel, QC, Canada, J7J 0C4 Fax: 450-668-2695 

Phone: 450-668-3033 Toll Free Canada: 1-888-664-1406 Toll Free USA: 1-888-920-6284

Содержание 023-064 Series

Страница 1: ...or by any means electronic mechanical photocopying recording or otherwise without the prior written permission of Parker Hannifin Canada Micro Thermo Technologies is a trademark of Parker Hannifin Ca...

Страница 2: ...ettings list 8 3 3 Test 8 4 Operation 9 5 Calibration 9 6 MT Alliance installation 10 7 To add a missing Sensor model in the list 12 Safety Information This manual describes information required to in...

Страница 3: ...master slave operation or central control via a controller Pre calibrated plug and play sensor modules avoid the need to recalibrate when upgrading expired sensors Impact resistant water resistant enc...

Страница 4: ...C 88 F decreasing linearity to 50 rh at 40 C 104 F 1 5 User Interface Back lit LCD display shows gas concentration user settings and alarm status Red LED alarm indicators gas level 1 and 2 High inten...

Страница 5: ...to 5 feet 1 to 2 meters from the floor when the ceiling is 7 to 10 feet high If the ceiling height is higher than 10 feet for example for heavy equipment the carbon monoxide detectors are installed at...

Страница 6: ...ual pull station panel 24Vac 5VA Transformer Sensor GND Sensor U Input To sensor node Binary Input from limit switch AL1 AL2 AL3 PWR BI S L H S R141b 123 10 Active Sensor Alarm PPM reading Jumper Up P...

Страница 7: ...ermine the threshold of Sensor A at which the relay should operate default is 400ppm Setting 1 A1Del is the set time default is 30 sec 2 A1Off is the reset time default is 20 sec The relay reset by it...

Страница 8: ...55 44 C temperature display 0 off 1 on Temp 0 1 0 45 audio alarm 3 off on Aud 0 1 1 49 Keyboard security lock 0 off 1 on KBL 0 1 0 50 Temperature modify correct TMod 9 9 C 51 High temperature alarm li...

Страница 9: ...concentration drops below the threshold AL1 is for relay settings AL2 is for alarm 2 settings and AL3 is for alarm 3 and buzzer settings See section 3 2 User settings list to change any setting The bu...

Страница 10: ...tration Type Local Source Micro Thermo Manufacturer and the Sensor Model and gas type you are going to monitor pre defined sensor model will be available in version MTA 8 5 For previous version create...

Страница 11: ...alarm You can use predefined values by clicking on Pick Alarm Settings button Select the Hardware tab to review the sensor manufacturer and model and where you can select the node and input where this...

Страница 12: ...nge accordingly to the table at section 1 3 Ordering information Electrical point values are constant and should always be 9 45V and 2V respectively Please pay special attention to put 1 of full range...