72-PHW-1033 R2.0 023-0388 Wall CO2 Leak Detect Spec&Install.docx 

RL 2022-02-09 

Page 3 of 4 

 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Addition of CO2 sensor model for MTA V5.X version  

 
Already added in version 7.0 (updated in 8.6) 

 

Create sensor in the menu “Configure-Sensor Model” for the following models  
Model on key 341: 023-0388 CO2 6000 ppm (4-20mA)  
 
The range and level of the relay must be changed specifically for the 023-0388 model  
Copy “CD2RMC Wall Sensor Transmitter 20mA.bmp” in the “C:\Alliance\Images\SensorModels” 
If “CDDn Wall Sensor Transmitter 20mA.bmp” is in the folder \Images\Sensor Models it could be used but is not 
exactly the same.  

Sensor Node 

 

nvoUniversal 

 

Input U 

 

GND 

MT-Display  nviPPM 

CO

2

 6000 ppm 

MT-Display 

and strobe 

installed on 

the wall 

outside of 

the room 

sign :  

If the value shown 

exceeds 5000 ppm 

DO NOT ENTER 

strobe 

Light 

Manual pull 

station 

961-0001 

strobe 

Light 

CO2 sensor on 

the rack and the 

strobe installed 

on the wall inside 

of the room 

255 ohms 

resistor must be 

installed at the 

sensor node 