PSH120-1200
2 Introduction
This manual refers to refrigeration dryers designed to guarantee high
quality in the treatment of compressed air.
2.1 Transport
The packed unit must:
• remain upright;
• be protected against atmospheric agents;
• be protected against impacts.
2.2 Handling
Use a fork-lift truck suitable for the weight to be lifted, avoiding any type
of impact.
2.3 Inspection
a) All the units are assembled, wired, charged with refrigerant and oil
and tested under standard operating conditions in the factory;
b) on receiving the machine check its condition: immediately notify the
transport company in case of any damage;
c) unpack the unit as close as possible to the place of installation.
2.4 Storage
If several units have to stacked, follow the notes given on the packing.
Keep the unit packed in a clean place protected from damp and bad
weather.
3 Installation
Y
For the correct application of the warranty terms, follow the instruc-
tions given in the start-up report, fi ll it in and send it back to Seller.
In places with fi re hazard, provide for a suitable fi re-extinguishing sys-
tem.
3.1 Procedures
Install the dryer inside, in a clean area protected from direct atmospheric
agents (including sunlight).
Y
Comply with the instructions given in par. 8.2 and 8.3.
All dryers must be fi tted with adequate pre-fi ltration near the dryer air
inlet. Seller is excluded any obligation of compensation or refund for any
direct or indirect damage caused by its absence
Y
Pre-fi lter element (for 3 micron fi ltration or better) must be replaced
at least once a year, or sooner as per manufacturer recommendations.
Y
Correctly connect the dryer to the compressed air inlet/outlet con-
nections.
The pipes and connectors in the air circuit are made of stainless steel.
The heat exchanger is made of stainless steel with copper braze-welding
It is recommended that you contact themanufacturer if the dryer is to be
used with particularly aggressive agents.
3.2 Operating space
Leave a space of 1.5 m around the unit.
Leave a space of 2 m above dryer models with vertical condensation air
expulsion.
3.3 Versions
Air-cooled version (Ac)
Do not create cooling air recirculation situations. Do not obstruct the
ventilation grilles.
Water-cooled version (Wc)
If not provided in the supply, fi t a mesh fi lter on the condensation water
inlet.
Y,
Inlet condensation water characteristics:
Temperature
≥50°F (10°C)
CL
-
<50 ppm
ΔT
IN/OUT
5-15°C
CaCO
3
70-150 ppm
Max % glycol
50
O
2
<0.1 ppm
Pressure
43.5-145 PSIg
(3-10 barg)
Fe
<0.2 ppm
PH
7.5-9
NO
3
<2 ppm
Electrical
conductivity
10-500 μS/cm
HCO
3
-
70-300 ppm
Langelier
saturation
index
0-1
H
2
S
<0.05 ppm
SO
4
2-
<50 ppm
CO
2
<5 ppm
NH
3
<1 ppm
Al
<0.2 ppm
Please note that for special cooling water types such as demineralized,
deionized or distilled it is necessary to contact the manufacturer to verify
which kind of condenser should be used since the standard material may
not be suitable.
3.4 Tips
To prevent damage to the internal parts of the dryer and air compres-
sor, avoid installations where the surrounding air contains solid and/or
gaseous pollutants (e.g. sulphur, ammonia, chlorine and installations in
marine environments).
The ducting of extracted air is not recommended for versions with axial
fans.
3.5 Electrical connection
Use approved cable in conformity with the local laws and regulations (for
minimum cable section, see par. 8.3).
Install a differential thermal magnetic circuit breaker with contact open-
ing distance 3 mm ahead of the system (RCCB - IDn = 0.3A) (see the
relevant current local regulations).
The nominal current In of the magnetic circuit breaker must be equal to
the FLA with an intervention curve type D.
3.6 Condensate drain connection
Y
Make the connection to the draining system, avoiding connection in
a closed circuit shared by other pressurized discharge lines. Check the
correct fl ow of condensate discharges. Dispose of all the condensate in
conformity with current local environmental regulations.
4 Commissioning
4.1 Preliminary checks
Before commissioning the dryer, make sure:
• installation was carried out according that given in the section 3;
• the air inlet valves are closed and that there is no air fl ow through the
dryer;
• the power supply is correct;
• with Wc version, open the cooling water circuit a few minutes before
starting the dryer.
4.2 Starting
a) Start the dryer before the air compressor;
b) switch the power on by turning the MAIN SWITCH “
&
” to
“I ON”: the POWER LED (2) lights up turning yellow; the crankcase
heater will now start heating .
!
THE CRANKCASE HEATER MUST BE SWITCHED ON 12 HOURS
BEFORE STARTING THE DRYER.
Failure to comply with this rule may cause serious damage to the
compressor.
Once the crankcase is preheated, press the ON button on the control
panel.
c) press
x
: the POWER LED (2) turns green and the compressor
switches on; the dew point is displayed.
Y
Fans (Ac version): if connected with the wrong phase sequence
they turn in the opposite direction, with the risk of being damaged (in this
case the air exits the dryer cabinet from the condenser grilles instead
from the fan grille - see par. 8.6 and 8.7 for correct air fl ow); immediately
invert two phases.
d) Wait 5 minutes, then slowly open the air inlet valve;
e) slowly open the air outlet valve: the dryer is now drying.
Phases Monitor
If appears to display the alarm “CP “, during the start up of the dryer, the
user must verify the wiring of the input terminals of the disconnecting
switch of the dryer.
4.3 Operation
• Leave the dryer on during the entire period the air compressor is work-
ing;
• The dryer operates in automatic mode, therefore fi eld settings are not
required;
• In the event of unforeseen excess air fl ows, by-pass to avoid over-
loading the dryer.
Содержание Polestar-HP Smart PSH1000
Страница 2: ......
Страница 110: ...8 5 EXPLODED DRAWING 12 PSH120 1200 A B E D C 12 15 B3 4 5 1 8 3 9 2 B1 34 PSH 120 230 Ac ...
Страница 111: ...8 5 EXPLODED DRAWING 13 PSH120 1200 B A E D C 34 15 12 9 B3 1 2 2 3 8 4 5 B1 4 5 PSH 290 460 Ac ...
Страница 112: ...8 5 EXPLODED DRAWING 14 PSH120 1200 4 5 B1 3 3 1 8 2 34 15 9 12 B3 4 4 5 5 A B E D G C PSH 630 Ac ...
Страница 113: ...8 5 EXPLODED DRAWING 15 PSH120 1200 A B E D C 4 4 4 4 5 5 5 5 3 3 8 2 2 1 34 12 B3 15 9 B1 PSH 800 1200 Ac ...
Страница 114: ...8 5 EXPLODED DRAWING 16 PSH120 1200 34 15 9 B3 B E D C A 2 8 1 4 4 5 5 F G 22 B1 PSH 460 Wc ...
Страница 115: ...8 5 EXPLODED DRAWING 17 PSH120 1200 A F E D G C 34 15 9 B3 8 1 2 4 5 4 4 5 5 B1 B 22 PSH 630 Wc ...
Страница 116: ...8 5 EXPLODED DRAWING 18 PSH120 1200 4 4 4 4 5 5 5 5 B1 8 1 2 22 34 15 9 A C G B F E D PSH 800 1200 Wc ...
Страница 117: ...8 6 DIMENSIONAL DRAWING 19 PSH120 1200 PSH 120 230 Ac ...
Страница 118: ...8 6 DIMENSIONAL DRAWING 20 PSH120 1200 PSH 290 460 Ac ...
Страница 119: ...8 6 DIMENSIONAL DRAWING 21 PSH120 1200 PSH 630 1200 Ac ...
Страница 120: ...8 6 DIMENSIONAL DRAWING 22 PSH120 1200 PSH 290 460 Wc ...
Страница 121: ...8 7 REFRIGERANT CIRCUIT 23 PSH120 1200 PSH 630 1200 Wc ...
Страница 122: ...8 7 REFRIGERANT CIRCUIT 24 PSH120 1200 PSH 120 230 Ac ...
Страница 123: ...8 7 REFRIGERANT CIRCUIT 25 PSH120 1200 PSH 290 460 Ac ...
Страница 124: ...8 7 REFRIGERANT CIRCUIT 26 PSH120 1200 PSH 630 Ac ...
Страница 125: ...8 7 REFRIGERANT CIRCUIT 27 PSH120 1200 PSH 800 1200 Ac ...
Страница 126: ...8 7 REFRIGERANT CIRCUIT 28 PSH120 1200 PSH 490 460 Wc ...
Страница 127: ...8 7 REFRIGERANT CIRCUIT 29 PSH120 1200 PSH 630 Wc ...
Страница 128: ...8 7 REFRIGERANT CIRCUIT 30 PSH120 1200 PSH 800 1200 Wc ...
Страница 129: ...8 8 WIRING DIAGRAM 31 PSH120 1200 Sheet 1 of 6 PSH 120 230 Ac ...
Страница 130: ...8 8 WIRING DIAGRAM 32 PSH120 1200 Sheet 2 of 6 PSH 120 230 Ac ...
Страница 131: ...8 8 WIRING DIAGRAM 33 PSH120 1200 Sheet 3 of 6 PSH 120 230 Ac ...
Страница 132: ...8 8 WIRING DIAGRAM 34 PSH120 1200 Sheet 4 of 6 PSH 120 230 Ac ...
Страница 133: ...8 8 WIRING DIAGRAM 35 PSH120 1200 Sheet 5 of 6 PSH 120 230 Ac ...
Страница 134: ...8 8 WIRING DIAGRAM 36 PSH120 1200 Sheet 6 of 6 PSH 120 230 Ac ...
Страница 135: ...8 8 WIRING DIAGRAM 37 PSH120 1200 Sheet 1 of 6 PSH 290 460 Ac Wc ...
Страница 138: ...8 8 WIRING DIAGRAM 40 PSH120 1200 Sheet 4 of 6 PSH 290 460 Ac Wc ...
Страница 139: ...8 8 WIRING DIAGRAM 41 PSH120 1200 Sheet 5 of 6 PSH 290 460 Ac Wc ...
Страница 140: ...8 8 WIRING DIAGRAM 42 PSH120 1200 Sheet 6 of 6 PSH 290 460 Ac Wc ...
Страница 141: ...8 8 WIRING DIAGRAM 43 PSH120 1200 Sheet 1 of 6 PSH 630 Ac Wc ...
Страница 144: ...8 8 WIRING DIAGRAM 46 PSH120 1200 Sheet 4 of 6 PSH 630 Ac Wc ...
Страница 145: ...8 8 WIRING DIAGRAM 47 PSH120 1200 Sheet 5 of 6 PSH 630 Ac Wc ...
Страница 146: ...8 8 WIRING DIAGRAM 48 PSH120 1200 Sheet 6 of 6 PSH 630 Ac Wc ...
Страница 147: ...8 8 WIRING DIAGRAM 49 PSH120 1200 Sheet 1 of 6 PSH 800 1200 PSH 800 1200 Ac Wc ...
Страница 148: ...8 8 WIRING DIAGRAM 50 PSH120 1200 Sheet 2 of 6 PSH 800 1200 Ac Wc ...
Страница 149: ...8 8 WIRING DIAGRAM 51 PSH120 1200 Sheet 3 of 6 PSH 800 1200 Ac Wc ...
Страница 150: ...8 8 WIRING DIAGRAM 52 PSH120 1200 Sheet 4 of 6 PSH 800 1200 Ac Wc ...
Страница 151: ...8 8 WIRING DIAGRAM 53 PSH120 1200 Sheet 5 of 6 PSH 800 1200 Ac Wc ...
Страница 152: ...8 8 WIRING DIAGRAM 54 PSH120 1200 Sheet 6 of 6 PSH 800 1200 Ac Wc ...
Страница 153: ......