5  JBUS ADDRESS TABLE 

JBUS address

 (decimal)

 

Data 

JBUS function 

Model = 00C7h 

3, 4 

Version 

3, 4 

Power supply voltage (V/10) 

3, 4 

Temperature (°C) 

3, 4 

Quality 1s (1) (3) 

3, 4 

Distance 1s (2) (3) 

3, 4 

Quality 4s (1) (3) 

3, 4 

Distance 4s (2) (3) 

3, 4 

Quality 16s (1) (3) 

3, 4 

Distance 16s (2) (3) 

3, 4 

100 

Standby / reactivation 

command (4) 

65524 

Minimum clearance (mm) 

65525 

Maximum clearance (mm) 

6  

65529 

Clearance specified with 

fault (mm) 

6  

65533 

Sensitivity (5) 

6  

65535 

Slave number (*) 

 

(*)  1  by  default.  If  the  existing  slave  number  is  unknown,  use  the 
slave number 0 to enter the desired slave, connecting only one slave 
to the RS485 line. 
 
(1) Details of distance measurement quality: 
 

[15-8] = echo amplitude, 0 to 255 

 

[7] = presence of parasitic echoes 
[6-4] = sensitivity, 0 to 7 

 

[3-0] = number of valid echoes out of 1s, 0 to 15 

 
(2) Details of distance measurement: 
 

65535 (-1) = measurement in progress (following  

 

reactivation) 

 

65534  (-2)  =  measurement  in  progress  (internal  VCO 

 

reset) 

 

65533 (-3) = no echo 

 

65532 (-4) = power supply voltage too low 

 

65530 (-6) = echo removed by filtering (false echo) 

 

65529 (-7) = incorrect echo shape 
65528 (-8) = Echo outside authorised range 

 

0 – 30000 = valid measurement available (mm) 

 
(3)  The  radar  makes  several  measurements  per  second,  and  the 
averages  over  1s,  4s  and  16s.  The  3  values  are  available  in  the 
JBUS addressable space. The same applies for data relating to the 
quality of this measurement. 
 
(4)  By  default,  the  radar  is  activated.  Enter  the  value  256  at  the 
address 100 to put the radar to sleep and 0 to reactivate it. When the 
radar is on standby, the first JBUS query may not get a response. In 
this case, the master must repeat its request within 2s. 
 
(5) Most significant byte, from 0 to 7 

6  SAFETY SYMBOLS AND MARKS 

:

 

Hazard risk. Important information. Refer to the instructions for use. 

: Read the instructions for use. 

: Compliant with European Union and EFTA directives. 

: European Directive 2002/96/EC of 27 January 2003 on waste electrical and electronic equipment (WEEE 

Directive) was transposed in France by Decree No. 2005-829 of 20 July 2005. 
 Electrical or electronic appliances, and their spare parts and consumables must never be disposed of in household 
waste. 

PARATRONIC

 has undertaken to set up an Individual Collection System. 

PARATRONIC

 waste electrical and electronic equipment should be returned by customers (End users) to our 

company’s head office, at the following address: 

 

PARATRONIC

 - Zone Industrielle - Rue des Genêts, 01600 REYRIEUX, France 

Service Recyclage DEEE 

7  SAFETY INSTRUCTIONS 

: WARNING: 

The protection offered may be compromised if this appliance is not used as specified. 

 

 

The specifications described in this document are subject to change by the manufacturer without notice. 

Отзывы: