6
5. WIRING
5.1. ORDER OF WIRING
5.2. DRAWING OF WIRING
6. MODE SELECTING METHOD
6.1. SELECTING AUTO & MANUAL
DIP SWITCH -1
OFF : Selecting AUTO(4~20mA)
ON : Selecting MANUAL(10K
Ω
)
6.2. SELECTING SOFT UP/DOWN
Only for used in phase-angle control. No applicable for zero-crossing control.
And also current limit function is applicable when SOFT UP/DOWN is
working on.
Selecting switch is applicable only when
main switch is on.
To change selecting mode, please push re-set
button or re-start the unit.
DIP SWITCH -2
OFF : NO SOFT UP/DOWN function
ON : Selecting SOFT UP/DOWN (15 SEC.)
Pay attention to polarity (+,-) of input signal.
Connect mechanic relay(no voltage) onto Run/Stop.
Alarm relay is N.O.(Normal open).
6.3. OUTPUT VOLUME
DIP SWITCH -3
OFF : Using inner volume
⑥
on page 5)
ON : Using manual volume of 10k
Ω
6.4. SELECTING CONTROL METHOD
DIP SWITCH -4
OFF : Phase Angle control
ON : Zero-Crossing control
(Advanced Fixed 16mode)
Can not use manual mode and output
volume together.
6.5. SELECTING TEST MODE
DIP SWITCH -5
OFF : With Alarm Function
ON : Without Alarm Function
1
) Detach the covers (Top and bottom).
2) Connect R-S-T.(Caution : Be careful the cable
should not be touched onto the case)
3) Connect loads to U-V-W.
4) Connect FG (Field ground).
5) Attach the covers (Tope and bottom).
6) Connect fan power of 220VAC, if it is with
cooling fan.
L(in) (+) / V(in) option
L(in) (-) / V(in) option
Run / Stop
Com / VR-High
VR-IN
VR-Low
ALARM / 250VAC 1A
T
S
R
R
R
R