background image

c)

 

Install the new parallel system refers to the previous section. 

9)

 

Remove one unit from the parallel system 
There are two methods to remove one unit from the parallel system: 
First method: 

a)

 

Press the “OFF” key twice and each time should be lasted for more than 0.5s, then the UPS will enter 
into bypass mode or no output mode without output.   

b)

 

Turn off the output breaker of this unit, and then turn off the input breaker of this unit. 

c)

 

After it shutdown, you can move the parallel cable and share current cable. And then remove the unit 
out of the parallel system. 

Second method: 

a)

 

If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the load 
and shut down the system first. 

b)

 

Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPS will 
transfer to bypass mode.   

c)

 

Remove all the maintenance bypass covers and set the maintenance switches from “UPS” to “BPS”.   

d)

 

Turn off all the input breakers and battery breakers in parallel system.   

e)

 

Turn off the output breaker and move the parallel cable and share current cable of the UPS which you 
want, then remove it out of the parallel system. 

f)

 

Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode.

 

Set the 

maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back.   

g)

 

Turn on the remaining UPS according to 5). 

 

 

Version 

Date 

Modification 

1.0 

20120810 

New create 

1.1 

20140805 

Some words correction 

2.0 

20140902 

For  UPS  with  isolation  output  transformer,  need to join  the neutral at 
the

 input terminal 

of each UPS together.

 Because the input breaker of 

the UPS never cut OFF the neutral.

 

3.0 

20150324 

Add 30K to the SOP and some small issue corrected. 

4.0 

20160130 

Modify the control boards necessary for parallel description 

 

 

 
 

Содержание Galleon

Страница 1: ...llowing picture is just for reference 2 Installation Warning For standard model Make sure the UPS is not turned on before installation The UPS should not be turned on during installation Cut off all t...

Страница 2: ...ifferent between these two boards the part number The beginning 10 number of the series number and firmware label Label on the MCU in the picture just for reference different version UPS may have diff...

Страница 3: ...control board demount the small PCBA board Demount the 3 white screws disconnect the 50 pin cable Replace the PFC control board with a new one It is better assemble the small PCBA first then assemble...

Страница 4: ...unt the screw Then pull the INV control board Flipping over the INV control board you can see the glue on the connectors remove the glue then dis connect all the cables Replace the INV control board w...

Страница 5: ...the cables on the communication board and demount the srews that used to fasten the communication board to the rear panel Replace the board with a new one connect the cables install the screws 2 3 Par...

Страница 6: ...nect CN001 to CN15 of INV1 2 board Connect CN002 to CN16 of INV1 2 board Connect CN003 to CN15 of INV3 board Step 5 Connect the wires that demounted from the OP EMI board by step2 Connect R1 to P1 of...

Страница 7: ...upply cable to CN9 of parallel board Connect the S phase current equalizer cable to CN10 of parallel board Connect the T phase current equalizer cable to CN11 of parallel board Step 8 Remove covers fo...

Страница 8: ...rt red black cable to CN10 of communication board Step 11 Connect the S phase current equalizer cable the longer red black cable to CN20 of INV 1 2 board Step 12 Connect the T phase current equalizer...

Страница 9: ...board Connect the 14 pin grey cable to CN11 of INV control board Step 14 Assemble the INV control board back to INV1 2 board and then make the 14 PIN grey cable through the middle iron board Step 15 C...

Страница 10: ...Long Backup Unit 3 Wiring Connection for Parallel Operation Please follow the below steps to connect cables and wires for Gallon 3 3 parallel models Step 1 Parallel cable and share current cable conne...

Страница 11: ...each UPS to an output breaker 4 Connect all output breakers to a major output breaker Then this major output breaker will directly connect to the loads Step 3 If the UPS is connected to external batt...

Страница 12: ...onverter enable or disable f bypass enable or disable g bypass open or forbidden h frequency auto detect enable or disable i inverter short clear enable or disable 3 Turn on the UPS into the line mode...

Страница 13: ...ve this setting into EEPROM Output A voltage calibration Interface Setting Parameter 2 it always shows OP V as output voltage Parameter 3 it shows the internal measurement value of the output A voltag...

Страница 14: ...arallel system supplies power to the loads via the bypass c Check the LCD whether displays the parallel information as showed in the below picture If parallel UPS systems are successfully set up it wi...

Страница 15: ...breaker only for long run model and output breaker of each UPS c Press the ON button of one UPS to set up the power supply UPS will enter to power on mode After initialization UPS will enter to No Out...

Страница 16: ...stem All UPS will transfer to bypass mode c Remove all the maintenance bypass covers and set the maintenance switches from UPS to BPS d Turn off all the input breakers and battery breakers in parallel...

Отзывы: