30
R
EFERENCE
& I
NSTALLATION
M
ANUAL
8.3
TAMPER RECOGNITION
Section [132]: Zone Options
[1] OFF / [2] OFF: Tamper Recognition Disabled (default)
If the system is armed or disarmed, the control panel will display the zone as open in the keypad display, but will not generate
an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON: Trouble Only
If the system is armed and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). If the system is disarmed and a tamper wiring failure occurs on a zone, a Tamper/Zone Wiring Failure will appear
in the keypads’ Trouble Display (see page 47) and the control panel will transmit the appropriate Zone Tamper report code (see
page 34).
[1] ON / [2] OFF: Silent Alarm
If the system is armed and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). In a disarmed system, it functions the same as the Trouble Only setting, but it will also generate a silent alarm. A
silent alarm will not trigger any bells or sirens, but the system will have to be disarmed.
[1] ON / [2] ON: Audible Alarm
In an armed system and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). In a disarmed system, it functions the same as Trouble Only setting, except it will also generate an audible
alarm.
8.3.1
T
AMPER
B
YPASS
O
PTIONS
Section [132]: Zone Options
Option
[3]
OFF = Will generate a tamper if detected on a bypassed zone (default)
Option
[3]
ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the control panel
will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper Recognition ignores the bypass
definition. This means the control panel will generate an incident as per Tamper Recognition settings if a tamper or
wire fault occurs on a bypassed zone.
8.4
KEYPAD PANIC OPTIONS
Section [128]: General Options
Option
[1]
OFF = Emergency Panic Disabled (default)
Option
[1]
ON = Emergency Panic Enabled
Pressing the [1] and [3] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [4].
Option
[2]
OFF = Auxiliary Panic Disabled (default)
Option
[2]
ON = Auxiliary Panic Enabled
Pressing the [4] and [6] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [5].
Option
[3]
OFF =
Fire Panic Disabled (default)
Option
[3]
ON =
Fire Panic Enabled
Pressing the [7] and [9] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [6].
Option
[4]
OFF = Emergency Panic is Silent (default)
Option
[4]
ON = Emergency Panic is Audible
Option
[5]
OFF = Auxiliary Panic is Silent (default)
Option
[5]
ON = Auxiliary Panic is Audible
Option
[6]
OFF = Fire Panic is Silent (default)
Option
[6]
ON =
Fire Panic is Pulsed
Silent alarm:
The control panel emits a Confirmation Beep and transmits the appropriate Panic report code if programmed in section [195]. The
control panel will not enable the keypad buzzers or the control panel’s
BELL
output (no audible alarm).
Audible alarm:
Same as silent alarm, except the keypad buzzers and the
BELL
output will activate until a user cancels the alarm (disarms) with a
valid User Access Code or when the Bell Cut-Off Timer elapses (see page 29).
Fire (pulsed) alarm:
Same as audible operation, except that the
BELL
output will be pulsed as shown in Figure on page 20.