Entering section [020] will activate the PGM for 8 seconds to verify if the
PGM is functioning properly.
The value programmed in section [002] represents how long the Power
Supply Module will wait before reporting an AC power failure to the control
panel. To program the timer, enter a 3-digit decimal value (000 to 255
minutes) into section [002]. Default: Instant reporting (000).
S
PECIFICATIONS
AC Power:
16Vac, 20/40VA, 50 - 60Hz
Aux. Power:
12Vdc, typical 600mA, 700mA max.
Battery:
12Vdc, 4Ah minimum
Number of Outputs:
1 form “C” relay rated @ 125V, 5A receptive load
Control Panel
Compatibility:
Any Digiplex (DGP-48) or DigiplexNE (DGP-NE96)
Specifications may change without prior notice.
Section [020]
PGM Test Mode
Section [002]
AC Failure Report Delay
Figure 1: Connecting the DGP2-PS17