INSTALLATION AND TEST

NOTE:  If a Battery Pack is used with this UPS, refer first to the Battery Pack Owner's
             Manual Installation Procedure.

1.   Ensure that the UPS power switch is "Off" ("        " position).  Plug the UPS Power Plug into a

grounded commercial power receptacle with proper supply voltage and frequency.

2.  Turn the DC Breaker Switch on.

3.  Turn the UPS Power Switch "On" ("I" position).  With commercial voltage present and in

range, the UPS will come on in the AC mode after a short delay.

4.  Press and hold the Test/Alarm Silencer button for approximately 30 seconds: the AC

NORMAL LED will extinguish.  The BATTERY IN USE LED will light, the BATTERY STATUS
LED's will light and the Audible Alarm will sound after a short delay.  Release the Test/Alarm
Silencer Button and the UPS will return to the AC Normal mode after a short delay.  AC
NORMAL LED will be on and all other indicators off.

5.  Verify that the power requirements (VA & watts) of the equipment to be protected are within

the capacity of the UPS.  Plug in and turn on the various loads.  Momentarily press the Test
Button and verify proper UPS operation.

NOTE:  If any condition experienced during the above test procedure was not as
             described, refer to the UPS Problem Chart in the back of this manual.

OPERATION

The UPS loads may be controlled by the UPS Power Switch if desired.  For Model MM450, the
battery charger functions with the Power Switch on or off.  For other models, the Power Switch
must be on for battery charge; consequently, these units may need to remain on overnight if
several  power outages occurred during the day.

When a brownout, power interruption, power outage or over-voltage condition occurs, the alarm
will sound and the BATTERY IN USE light indicator will glow, indicating that commercial power is
lost or unacceptable and MINUTEMAN is now supplying power to your system.  With a slower
intermittent audible alarm (approximately once every two seconds) and one or more green
BATTERY STATUS indicator lights on, the unit is in the normal Inverter mode (BATTERY
OPERATION).  When the alarm sounds at more rapid intervals (approximately two per second)
and all green BATTERY STATUS lights extinguish, about two minutes of battery power remain.  If
you have not already downloaded you system and turned it off, you must do so at this time.  Then
the MINUTEMAN Power Switch should be turned off to prevent further battery discharge.

When commercial power returns, switch the MINUTEMAN power switch to the "On"  position if it
was turned off previously.  The green indicator light will come on after a short delay.  Return your
system to operation, and the MINUTEMAN system will automatically recharge the internal
batteries during system operation.

Since most commercial power outages are of short duration, commercial power will probably be
restored before the two-minute warning.  IF COMMERCIAL POWER RETURNS BEFORE THE
WARNING SIGNAL, THERE IS NO NEED TO SHUT DOWN
 THE SYSTEM AT ALL.  The
MINUTEMAN will switch back to normal AC operation automatically.

Содержание MM450

Страница 1: ...Minuteman Series User s Manual...

Страница 2: ...its 3 7 Electrical Specifications 4 8 Computer Back Up Time vs Load 5 9 Physical Specifications 6 10 Typical Runtime vs Load Minutes 6 11 Unit Description 7 12 Installation and Test 8 13 Operation 8 1...

Страница 3: ...er your warranty Failure to register your warranty renders it non valid IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Read this manual carefully before operating the UPS All instructions shoul...

Страница 4: ...the skin and eyes and may be toxic CAUTION Although battery system voltages are only 24 or 48 volts battery systems can still present a risk The current capability of a battery is sufficient to burn w...

Страница 5: ...be used with each Minuteman UPS without any output power derating MINUTEMAN UPS INTERNAL BATTERY SYSTEM BP TO BE USED MM450 24VDC 7 AMP HOUR BP24V10 10 AMP HOUR MM850 48VDC 7 AMP HOUR BP48V10 10 AMP H...

Страница 6: ...ls Input Voltage AC Mode Function 120VAC 15VAC 220VAC 30VAC Input Frequency Deviation for Synchronization 5 Inrush Current 1 5x Rated Surge Protection 3 way meets IEEE STD 587 RFI EMI Noise Filtering...

Страница 7: ...5 COMPUTER BACK UP TIME vs LOAD Internal Battery System or Standard Battery Pack COMPUTER BACK UP TIME vs LOAD UPS with Optional Battery Pack...

Страница 8: ...C to 40 C 5 F to 104 F Relative Humidity 95 Max Non Condensing Maximum Altitude Without Derate 15 000 Ft Acoustic Noise Less than 60dB 3 TYPICAL RUNTIME vs LOAD MINUTES COMPUTER MM450 W MM850 W MM130...

Страница 9: ...binations of locking and straight blade receptacles Optional International Plugs LEDS AC NORMAL Green when commercial voltage is in range and present provided battery circuit breaker is closed off oth...

Страница 10: ...off For other models the Power Switch must be on for battery charge consequently these units may need to remain on overnight if several power outages occurred during the day When a brownout power int...

Страница 11: ...will allow direct interface with many different computer operating systems This capability permits an unattended orderly shut down of the computer system when commercial power is lost for a long perio...

Страница 12: ...n problems appears on the last page Do not remove the unit cover or attempt any service There are no user serviceable components inside Unauthorized service will void the warranty POLICY AND INSTRUCTI...

Страница 13: ...ount or the estimated cost plus shipping and handling UPS PROBLEM CHART PROBLEM POSSIBLE CAUSE ACTION TO TAKE When UPS Power Switch is turned on UPS stays in Inverter mode Input fuse blown or input br...

Страница 14: ...lowing terms and conditions Para Systems or its designated representative will at Para Systems option repair or replace any equipment so damaged provided the cost of repair or replacement of the equip...

Отзывы: