PAN-14 Sensor Installation Guide
Revision 1.1 April 20, 2016
6
Unpacking the Hardware
Sensors are shipped in 3-unit packs.
•
CTs are not included and can be bought separately.
Safety Precautions
•
The sensor must be installed only on an insulated conductor.
•
CTs output/secondary current
must not
exceed 5A.
•
The sensor and CT should be installed and removed only by a qualified
electrician.
•
Installation must not be performed on a live wire for reasons of safety
and random shock hazard. Power supply to the panel must be shut off
before and during installation.
•
The sensor and CT must not be installed lying or touching bus bars or
any other non-insulated, exposed conductors.
•
Installation is possible both on external entry/exit conductors before the
terminal strip, as well as both ends of the circuit breaker. The least
cramped, most accessible location should be chosen for installation. The
sensor should be installed such that the arrow points in the direction of
the load.
Caution!
Protection provided by the equipment can be impaired if used in a
manner not specified by the manufacturer.
Mapping the Site
See Panoramic Power Deployment Guide.
(P/Ns PAN-14-US, PAN-14-EU)