background image

FIGURE 8:  INSERT and CENTER the RUN-WIRE,

                  TIGHTEN HEX BOLT UNTIL THE 

                  RATED TORQUE IS ACHIEVED

                  AND MAINTAINED FOR 5 SECONDS

MAIN FASTENER SIZE

VSC6:  5/16" SAE HEX

VSC3/0:  3/8" SAE HEX

Insert wire fully until

"Locating Mark" is flush 

with connector body

at the wire insertion ports

FIGURE 7:  INSERT SENSOR LEADS AND SECURE

                  (TORQUE TERMINAL SCREWS) 

Use Torque-driver

(T10 Torx) to tighten

Terminal Screws to

Specified Torque.

Refer to Connector Ratings

Information (table) below

KEEP RUN WIRE

CENTERED WITH

THE CIRCULAR RECESS

OF OPENING

Page 3 of 3

For Technical Support:   www.panduit.com/resources/install_maintain.asp

Step-by-Step Installation Procedure (

continued from page 2 of 3

):

9.       See FIGURE 7:  Insert a crimped, color-coded pair of AVT sensor leads into TAP WIRE terminals.

10.     See FIGURE 7:  Verify fully-inserted AVT sensor leads by verifying "location mark" is flush with connector ports.

11.     See FIGURE 7:  Use torque-driver (T10 Torx) to tighten terminal screws to specified Torque, as listed on Connector

                                    packaging and provided in Connector Rating Information (see below).

Connector Rating Information:

12.     See FIGURE 8:  Properly position Connector onto phase conductor (RUN WIRE) and keep RUN WIRE centered

                                    with the circular recess during next step.

13.     See FIGURE 8:  Use torque-driver (SAE Hex) to tighten hex bolt, while keeping RUN WIRE centered with the

                                    circular recess of opening, until the specified Torque is achieved and maintained for 5 seconds.

                                    Specified Torque is provided on Connector packaging and in Connector Ratings Information below.

WIRE 

CONNECTOR

587H

PANDUIT CATALOG P/N

VSC6 VSC3/0

MAX. Operating Temperature ( C)

90 C

90 C

MAX. Operating Voltage (Volts)

600V

600V

RUN WIRE

Torque-driver Installation Tool,

SAE Hex Size (Main Fastener)

5/16"

3/8"

Installation Torque (Required)

40 in-lb 80 in-lb

Minimum Rated Wire Range, AWG

14 SOL

14 STR

4 SOL

4 STR

Maximum Rated Wire Range, AWG

6 STR

3/0 STR

TAP WIRE

Torque-driver Installation Tool Bit Size

(Recommend Wiha Tool P/N 28502)  T10 Torx T10 Torx

Installation Torque (Required)

7 in-lb

7 in-lb

Rated Tap Wire Size, AWG

(terminated with F80-12-M ferrule)

14 STR

Class K

14 STR

Class K

Required Ferrule, Panduit Catalog P/N

& Crimp Tool, Panduit Catalog P/N

F80-12-M

CT-1160

 T-PMPI-322-PC 

(revision 02)

                          INSTALLATION INSTRUCTIONS                                        

Panduit Corp. 2018

C

VeriSafe  Insulation-Piercing Connector:  VSC Series

VeriSafe  Insulation-Piercing Connection Kit:  VS-CKP Series

for

 VeriSafe  Sensor Lead Tapping on Cu-Only Conductors

TM

TM

TM

Отзывы: