background image

 0.875" 

AFTER PROPER TERMINATION OF FERRULE,

MARK LINE ON CONDUCTOR INSULATION

FROM END OF CRIMPED FERRULE

STRIP

SENSOR LEAD

INSULATION 

FERRULE F80-12-M

FIGURE 2:  CONNECTOR FEATURES

T10 TORX TERMINAL SCREWS are accessible 

from the two ports and are used to ADJUST 

TERMINALS inside the CONNECTOR.  TERMINALS 

are used to SECURE a PAIR of COLOR-CODED, 

FULLY-INSERTED and PROPERLY-CRIMPED TAP 

WIRES (AVT Sensor Leads) within TERMINALS 

INSERTION PORTS for FULLY-INSERTED 

and PROPERLY-CRIMPED TAP WIRES

(AVT Sendor Leads) into TERMINALS

INSIDE THE CONNECTOR

MAIN FASTENER

Page 1 of 3

For Technical Support:   www.panduit.com/resources/install_maintain.asp

FIGURE 1:  PREPARATION OF FERRULES

                 ONTO SENSOR LEADS

Step-by-Step Installation Procedure:  

Always de-energize panel and verify absence of voltage before installation.

See FIGURE 1:  Prepare (strip) AVT device sensor leads

1.

See FIGURE 1:  Crimp ferrules F80-12-M onto sensor seads

2.

See FIGURE 1:  Make locating mark on sensor leads

3.

See FIGURE 2:  Review connector features

4.

See FIGURE 2:  Loosen factory-tightened MAIN FASTENER at least 6 full turns before proceeding to next step. 

5.

CONNECTION KIT

CATALOG

PART NUMBER

"RUN" WIRE RANGE

(CODE WIRE)

"TAP" WIRE AWG

(Terminated with Ferrule)

CONNECTOR

FERRULE

Min.

Max.

CATALOG 

P/N

QUANTITY CATALOG 

P/N

QUANTITY

VS-CKP14-6

14 AWG SOL

14 AWG STR

6 AWG SOL

6 AWG STR

14 AWG STR Class K

(Terminated with Ferrule)

VSC6

3

F80-12-M

12

VS-CKP4-000

4 AWG SOL

4 AWG STR

3/0 AWG STR

VSC3/0

3

F80-12-M

12

VeriSafe  Insulation-Piercing Connector:  VSC Series

VeriSafe  Insulation-Piercing Connection Kit:  VS-CKP Series

 

for

 VeriSafe  AVT Sensor Lead Tapping on Copper Conductors

IMPORTANT

 

READ THIS ENTIRE INSTRUCTION SHEET BEFORE ATTEMPTING TO INSTALL THE CONNECTOR

.

                       

READ THE ENTIRE VERISAFE   AVT ABSENCE OF VOLTAGE TESTER INSTRUCTION MANUAL (B21052

, OR EQUIVALENT

)

                       PROVIDED WITH THE AVT DEVICE OR DOWNLOAD CURRENT MANUAL FROM                                  .

C

Panduit Corp. 2018

                          INSTALLATION INSTRUCTIONS                                        

 T-PMPI-322-PC 

(revision 02)

TM

TM

TM

Safety Information:

PANDUIT VSC Series Insulation-Piercing Connectors are intended for use in simplifying installation and connection of 

PANDUIT VeriSafe   AVT Absence of Voltage Testers to phase (run) conductors, per electrical code requirements, within 

the rated environmental and operational limitations according to regulatory / safety standard certifcations or listings.

Always DE-ENERGIZE panel and VERIFY for absence of voltage in panel before attempting to install connector.

Installer must ALSO follow all safety, installation, commissioning and operating steps from the AVT Device Manual.

Connector is intended for one-time installation and use only!  Do not reuse nor re-install connector.

www.panduit.com

Connection Kit Contents:  

Connection Kits contain connectors and ferrules to install the AVT Device per below;