1
Technical Reference 49-SZ
Description
This Technical Reference describes how to ground PVIQ Patch Panels.
Performing the Procedure
Attaching ground kits to the jack modules
1. Attach the jumper to the jacks on the back of the P
AN
V
IEW
™ Patch Panel(s), insert the jumper
grounding wire through the grounding clip, and then attach the clip assembly onto the jumper
kit wire.
Grounding PVIQ Panels
Applies to:
SmartZone PVIQ Patch Panels
Objective:
The purpose of this Technical Reference is to demonstrate how PV
I
Q™
Patch Panels can be grounded when using shielded M
INI
-C
OM
™
Jacks
(e.g. CJS6X88TGY, CJS688TGY, CJS5E88TGY).
Pre-Requisites:
•
PANDUIT Equipment Jumper Kit (part # RGEJ1057PFY)
•
(24) PANDUIT Shielded Jack Module Jumpers (part # CJSGK
includes 10 jumpers in each Kit)
Published:
7/25/18