Panduit SmartZone EPA126 Скачать руководство пользователя страница 7

 

Version 1. April 2017 

 

SmartZone DCIM is not receiving events/alarms or health status from Gateway EPA126 

 

 

– 

 

Action:  

• 

Check if Gateway EPA126 has any active events 

• 

Check if the Enable flag has been turned off in Input Sensors>Configure screen 

• 

Check Gateway EPA126 

SNMP Rec’rs tab and verify IP, Community strings, and 

Access 

• 

Send a test alarm to the SNMP receiver 

 

Temperature sensor reporting an alarm 

– 

 

Symptoms: 

 

A red icon   

   or amber  

   icon or is 

missing

 for a sensor 

 

 

– 

 

Action:  

• 

Check thresholds setting for the specific sensor to make sure it is in range of 
Panduit specs 

• 

Ensure that sensor patch cord is connected properly  

• 

Verify that sensor is detected by Gateway EPA126 as a temperature type 

• 

Check if sensor name ‘Channel’ matches with sensor type

 

• 

Ensure sensor is in Enabled state 

• 

Switch the sensor to an empty port, 11 or 12 on Gateway EPA126, and check if 
the problem persists 

• 

Sensor may have been damaged/malfunctioning. Contact Panduit System 
Support 

 

 

 

 

 

Содержание SmartZone EPA126

Страница 1: ...8 Cannot ping the Gateway EPA126 10 Gateway EPA126 displaying an alarm Red Alarm LED on 10 Gateway EPA126 unit has been reset 10 Connectivity between Gateway EPA126 and PDU lost 11 How to audit Gatewa...

Страница 2: ...Resolution 1 PDU Port Enabled but PDU not physically connected In this situation the unused PDU ports may be enabled but not physically connected to a PDU Example a cabinet may contain 2 PDU s but all...

Страница 3: ...st Comms alerts from these ports F Selecting the port will take you to the screen shown below Set the Device Type field to Disabled This should prevent any further Lost Comms alerts from the disabled...

Страница 4: ...d to the PDU port that is generating the alert C If the Gateway EPA126 connection is present and is secure make sure the relevant patch cable is connected to the PDU monitoring port on the PDU itself...

Страница 5: ...ort Enabled but Sensor not physically connected In this situation the unused Sensor ports may be enabled but not physically connected to a Sensor Example a cabinet may contain 3 Temperature Sensors bu...

Страница 6: ...the Sensor port which needs to be disabled E Selecting the port will take you to the screen shown below Set the Device Type field to Auto Detect This should prevent any further Lost Comms alerts from...

Страница 7: ...sensor reporting an alarm Symptoms A red icon or amber icon or is missing for a sensor Action Check thresholds setting for the specific sensor to make sure it is in range of Panduit specs Ensure that...

Страница 8: ...l settings on the browser If problem persists contact Panduit System Support as a hard reset may be required due to a firmware fault Gateway EPA126 Reset Gateway EPA126 hard reset If Gateway EPA126 is...

Страница 9: ...9 Version 1 April 2017...

Страница 10: ...arm Red Alarm LED on Symptoms Gateway EPA126 show a red alarm LED in front and rear of the Gateway EPA126 Action This is an indication of a sensor showing value exceeding the set threshold limit Log i...

Страница 11: ...isplay panel driven by low voltage supply from Gateway EPA126 is enabled on the PDU NOTE The Gateway EPA126 disconnection to the PDU does not affect the power supply to PDU outlets It only affects mon...

Страница 12: ...s down in the cabinet how to get access inside the cabinet Symptoms Cabinet power offline or no power to Gateway EPA126 Door lock LEDs are off Action Access control on cabinet is via HID reader cards...

Страница 13: ...Panduit Support Client Name Location Incident or Issue Number if you have one for reference Short Description Any steps taken so far to address the issue Software and firmware versions plus P Ns if k...

Отзывы: