RMS Compact II
Version 1.0.7 September 2016
Page 38
For example, a hysteresis value of 5 would mean that in the case of an Upper Control
Limits alarm the alarm value would have to reduce to 5 below the threshold value
before another alarm is issued.
Please see Appendix B: Hysteresis Demystified for detailed information.
Limits and Traps
Defaults values for sensor alarm thresholds can be specified here. The default settings
for alarm threshold traps can also be specified here.
The thresholds than can be set are as follows:-
Upper Control Limit
Upper Warning Limit
Lower Warning Limit
Lower Control Limit
Default trap settings can also be applied for all of these thresholds. With the trap box
un-ticked no SNMP alarm traps will be generated even when an alarm condition
exists for that threshold.
Repeat Timer
The repeat timer causes alarm traps to be reissued after a specified amount of time if
the alarm condition remains present.
Setting the repeat timer to zero (0) will disable the repeat traps.