Panduit PViQ Скачать руководство пользователя страница 11

PViQ Switched POU 

 

 

 

Version 1.0 

11 

 

Network Setup 

Network Overview 

This product comes preconfigured with a default IP address set.  Simply connect to the POU and access 
the web page with your browser.   

Default IP Address 

The PViQ Switched units have a default IP address for initial setup and access to the unit if the assigned 
address is lost or forgotten.  Once an IP address is assigned to a unit, the default IP address is no longer 
active.  To restore the default IP address, press and hold the reset button located below the network 
connector for 20 seconds.  The idle and activity lights on the network connector will both light up when the 
IP address has been reset.  The reset button is accessed through the white, circular hole located below 
the Ethernet jack.   
   

Note:

 Pressing the reset button under the network connector will restore the default IP address and will 

also clear all password settings.  
  
The Configuration page allows you to assign the network properties or use DHCP to connect to your 
network.  Access to the unit requires the IP address to be known, so use of a Static IP or reserved DHCP 
is recommended.  The default address is shown on the front of the unit:  
  

 

IP Address:

     192.168.123.123  

 

Subnet Mask:

  255.255.255.0  

 

Gateway:

    

192.168.123.1  

Initial Setup 

1.  Connect POU to your computer using a crossover cable. 
2. 

On  your  computer,  go  to  “Start  >  Settings  >  Control  Panel  >  Network  and  Dial  Up 
Connections.” 

3. 

Right Click on “Local Area Connection” and select “Properties.” 

4.  Sel

ect the option to “Use the following IP address” and enter: 

 

IP address

:  

 

192.168.123.1 

Subnet mask

:    

255.255.255.0 

Default gateway

:  

192.168.123.1

2

 

 

5. 

Click “OK” twice. 

You can now access the unit using your web browser at the permanent IP address of 192.168.123.1. 

 

                                                      

2

 In some configurations, leaving the gateway field blank may resolve connectivity issues. 

Содержание PViQ

Страница 1: ...MN028 Version 2 0 Panduit PViQ Switched POU User Manual Switched and Environmental Monitored Switched with Per Outlet Power and Environmental Monitored...

Страница 2: ...hotocopying recording or otherwise without written permission from PANDUIT No patent liability is assumed with respect to the use of the information contained herein Although every precaution has been...

Страница 3: ...tup 11 WEB INTERFACE 13 Overview 13 Sensors Page 13 Logging Page 15 Display Page 16 Alarms Page 17 Control Page 18 Control Actions Tab 18 Control Settings Tab 19 Configuration Page 20 Configuration Ne...

Страница 4: ...35 Connecting Remote Sensors 36 Data Logging and Display 36 REMOTE OUTLET SWITCHING 37 Actions 37 Configuration 38 Power On Actions 38 ACCESSORIES 39 Remote Display 39 IP Addressable Network Cameras...

Страница 5: ...s plus additional current sensors to monitor individual outlet current Optional external sensors and network cameras are also available Environmental Temperature Operating 10 C 50 F min 45 C 113 F max...

Страница 6: ...o the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation This C...

Страница 7: ...er current conditions A Listed circuit breaker is required within the building installation The circuit breaker should be sized according to the POU s nameplate ratings and local national electrical c...

Страница 8: ...Strip Mounting Brackets can also be mounted to the rear equipment rails To center the 66 25 vertical power strips For 7 foot post racks mount L Bracket at RU spaces 03 and 43 For 8 foot 4 post racks m...

Страница 9: ...PViQ Switched POU Version 1 0 9 Toolless Mounting Hardware Use toolless buttons with key holed slots built into cabinet or with optional key holed brackets...

Страница 10: ...PViQ Switched POU 10 Version 1 0 Panduit Cabinet CS3...

Страница 11: ...rk connector will restore the default IP address and will also clear all password settings The Configuration page allows you to assign the network properties or use DHCP to connect to your network Acc...

Страница 12: ...PViQ Switched POU 12 Version 1 0 Typical Network Card Settings for PC or Laptop to connect to default IP address...

Страница 13: ...The front page Sensors gives both instantaneous and historical views of the unit s data Real time readings are provided for all power strip data outlet group data and sensor data next to historical gr...

Страница 14: ...PViQ Switched POU 14 Version 1 0...

Страница 15: ...onal remote display module Checked readings in the Logged Measurements section are logged into the data file at a rate of one point per minute and will be available for graphing and display Note that...

Страница 16: ...ors as well as change the default temperature unit of measure for external sensors The display page also allows the user to select between the default and classic web page layouts The default interfac...

Страница 17: ...establish alarm conditions for each sensor reading Alarm conditions can be established with either high or low trip thresholds The alarms are displayed in different sections based on the device the al...

Страница 18: ...page has two sub tabs Actions and Settings See Remote Outlet Switching for details Control Actions Tab The Actions tab on the Control page gives the user control of the outlets Outlets can be reboote...

Страница 19: ...ws the user to name and define a URL for outlets in addition to setting time delays for each outlet action Boot up status and sequential boot up options are also available All delay settings are refer...

Страница 20: ...ge has five sub tabs Network Monitoring Diagnostics Event Log and Admin See Unit Configuration for details Configuration Network Tab The user can enter and update the network settings on the Network t...

Отзывы: