background image

FOR TECHNICAL SUPPORT www.panduit.com/resources/install_maintain.asp

INSTRUCTIONS CM469D

© Panduit Corp. 2014

Part Number

PZRFE4U

PZRFE8U PZRFE12U

Mounting Bracket Depth Below Floor

5”

8.5”

12”

With Optional Cover 

7”

10.5”

14”

Enclosure Load Rating

18 lb

36 lb

54 lb

Page 1 of 5

P

AN

Z

ONE

 Raised Floor Enclosures

Part Numbers: PZRFE4U, PZRFE8U, PZRFE12U & PZRFC

The following items are included with PZRFE4/8/12

Required Tools

Installation:

Mounting Depth Table

PZRFE4U

PZRFE8U

*10mm Socket

(4) Support Brackets, with 

Washers and Nuts

(1) Enclosure with

 (4) Grommet Sleeves

1. Select the installation location ensuring there are no obstacles to interfere with the installation.
2. Mount the four support brackets under the enclosure by placing one on each pedestal mount bracket by attaching the U-bolt and nut 
around the pedestal (See Figure 2.1). Refer to Figures 4.1 through 4.3 for adjustment to various pedestal sizes. Use the magnetic ruler to 
measure the correct mounting location for each support bracket. Point them towards the center making a cross from the corners (See 
Figure 2.2). Ensure that the plate is allowed to pivot from side-to-side. 

Note:

 If Grid Runner is placed above pedestal plate, then the 

mounting assembly must be removed from plate and reconnected with the mounting assembly under the pedestal plate (See Figure 2.3).
3. Push CoolBoot Assemblies inside enclosure (See Figure 3.1) and then insert the enclosure in the desired floor tile.

PZRFE12U

Figure 2.1

Figure 2.2

Figure 3.1

(1) Lockable Enclosure Cover

(1) Set of Keys

Distance from bottom of pedestal head plate to top of mounting brackets.

(4) Bonding Bolts

Optional Components: PZRFC

(1) Magnetic Ruler

(+ .25” Tolerance)

Mounting assembly connected 
under pedestal mount plate.

Figure 2.3

*7/16” Socket

Отзывы: