INSTRUCTIONS CM408F
For Technical Support: www.panduit.com/resources/install_maintain.asp
3.2”
[82mm]
4.0”
[102mm]
B
A
C
D
10.5”
[267mm]
E
Width
Depth
A
B
C
D
E
23.6" [600mm]
47.2" [1200mm]
23.6" [600mm] 47.2" [1200mm] 40.7" [1035mm]
9.8" [250mm]
45.2" [1148mm]
27.6" [700mm]
47.2" [1200mm]
27.6" [700mm] 47.2" [1200mm] 40.7" [1035mm] 11.8" [300mm]
45.2" [1148mm]
23.6" [600mm]
39.3" [1000mm]
23.6" [600mm] 39.3" [1000mm] 33.6" [853mm]
9.8" [250mm]
37.3" [947mm]
27.6" [700mm]
39.3" [1000mm]
27.6" [700mm] 39.3" [1000mm] 33.6" [853mm]
11.8" [300mm]
37.3" [947mm]
Cabinet Dimensions
Mounting Distances
Page 6 of 24
Anti-Tip Brackets - Floor Mounting
N
ET
-S
ERV
Cabinets, whether stand alone or ganged with other cabinets, must always be anchored to the floor. The frame anchors
directly to the concrete slab or threaded rod via the included anti-tip brackets.
Assembly Sequence
1. Install the anti-tip brackets to the inside of cabinet frame, using (2) 5/16” bolts (1/2” socket) per bracket as shown below. Brackets
are slotted to allow for raising and lowering of cabinet.
(See leveling instructions on Page 4)
2. Attach the anchors to the floor with appropriate hardware for your type of floor. See Floor Anchoring Footprint view and chart below
for floor mounting dimensions.
NOTE:
Floor mounting bracket to be used when casters or leveling legs are installed. Bracket is to be reversed when casters are
installed. Reverse side of bracket allows for higher adjustment range with casters on cabinet frame.
Floor Anchoring Footprint
Anti-Tip
Brackets
Anti-Tip Bracket
(Bracket to be reversed
when casters are installed)
5/16” Bolts
(use 1/2” socket)
Floor Anchor Mounting
Locations
Frame
Mounting
Locations