INSTALLATION INSTRUCTIONS FS006

For Technical Support: www.panduit.com/resources/install_maintain.asp

Page 2 of 11

Enclosure Mounting Brackets

Figure 4

Determine where the cable will enter the enclosure. 
Carefully remove the knock-out at that entry location 
of the fiber tray so as not to damage surrounding 
sheet metal. DO NOT Install grommet at this stage, 
grommet will be installed after enclosure is mounted 
to rack.

Note:

 Cover removal is not required for proper 

fiber optic cabling installation.

To remove the cover if desired, unscrew the four 
#4-40 screws and lift cover up and off.

#4-40 screws

Use (2) #12-24 X 1/2" 
screws (provided). Repeat 
for other side.

Place enclosure mounting brackets at desired 
position on the rack. Mount the enclosure to the 
rack using (4) #12-24 x 12

"

 screws. Use (4)

M6 x 1 screws if mounting to a metric rack.

Figure 2

Figure 3

Figure 4A

Preparation and Rack Mounting

Содержание FCE1U

Страница 1: ...ble specification sheet for the specific cable in use Follow TIA EIA 568 A 569 606 and 607 installation guidelines where applicable Care should be taken when opening or closing a fully loaded drawer i...

Страница 2: ...at this stage grommet will be installed after enclosure is mounted to rack Note Cover removal is not required for proper fiber optic cabling installation To remove the cover if desired unscrew the fo...

Страница 3: ...sure Install grommet following the proper cutting diagram Cut the small circle for 1 diameter innerduct Cut the large circle for 1 1 2 diameter innerduct Cut the straight lines when not using any inne...

Страница 4: ...into the enclosure as shown Once mounted fully seat NyLatch fasteners to secure the cassette Figure 7 Figure 7A Cassettes Up to 4 for FEC1U FCE1UA Up to 8 for FCE2U Fully extend drawer to ensure prope...

Страница 5: ...not use so much slack that drawer cannot be returned to the home position See Fig 7C Use TAK TY Tape to secure fiber cords at cable entry location and other points as shown Drawer in extended position...

Страница 6: ...ation Position FAPs between upright flanges as shown Once mounted fully seat NyLatch fasteners to secure FAPs Slack Spools Field Termination or Pre Terminated Trunk Installation Figure 8 Figure 8A Iso...

Страница 7: ...approx 52 1 32m of individual fibers around slack spools Leave enough jacketed slack so when the drawer is fully extended the cables are not put under tension However do not use so much slack that dr...

Страница 8: ...top of each other and snap in place If 4 FOSMs are to be installed in the FCE1U or FCE1UA side latches on top module must be broken off to close enclosure drawer Position FAPs between upright flanges...

Страница 9: ...nd splice to pigtail per instructions in FS001 OPTICOM Fiber Optic Splice Module Installation Instructions Leave enough jacketed slack so when the drawer is fully extended the cables are not put under...

Страница 10: ...ing tray flange as shown Push grommet plunger through bend radius clip and sliding tray flange holes Finally fully seat plunger into grommet securing bend radius clip Bend Radius Control Clips Plunger...

Страница 11: ...uit com resources install_maintain asp Re install top cover front door and rear door assemblies if removed during fiber installation Attach Laser Warning Label and Caution Label where they are clearly...

Отзывы: