INSTALLATION INSTRUCTIONS

 © Panduit Corp. 2016

V00029KB

Page 3 of 6

Install Switch Ducting

Position Switch Ducting so that the perforated door of ducting faces the cold aisle and the mounting holes of Switch Ducting align with cage 
nuts in equipment rails 

(installed on page 2)

. Secure Switch Ducting to equipment rails using (5) #12-24 Phillips screw, (5) #12 External 

Tooth Washers and (1) hex head grounding screw 

(green; use 5/16” socket wrench)

 on front rail. Ensure that hex head grounding screws 

fasten into grounding cage nuts.

(1) #12-24 Hex Head 
Grounding Screws

(use 5/16” socket wrench)

Switch Ducting

Perforated Door of Switch Ducting

(faces Cold Aisle)

Install Switch Support Bracket

Position Switch Support Bracket so that the mounting holes of Switch Support Bracket align with cage nuts in equipment rails 

(installed on 

page 2)

.  Secure Switch Support Bracket to Rear equipment rails using (5) #12-24 Phillips screw, (5) #12 External Tooth Washers. (1) hex 

head grounding screw 

(green; use 5/16” socket wrench)

 on rear rail. Ensure that hex head grounding screws fasten into grounding cage 

nuts

.

Grounding Cage Nut

(green)

Cage Nuts

(installed)

(5) #12-24 Phillips Screws

(1) #12-24 Hex Head 
Grounding Screws

(use 5/16” socket wrench)

Cage Nuts

(installed)

Grounding Cage Nut

(green)

Switch Support 
Bracket

FRONT OF 
CABINET

REAR OF 
CABINET

FRONT OF 
CABINET

(5) #12 External Tooth Washers

(5) #12-24 Phillips Screws

(5) #12 External Tooth Washers