16.5.9.
Outdoor High Pressure Protection (H98)
Error code will not display (no OFF/ON Control Panel LED blinking) but store in EEPROM
Malfunction Decision Conditions:
During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor.
Malfunction Caused:
1. Faulty water pump.
2. Insufficient water flow rate in system.
3. Water leak in system.
4. Clogged expansion valve or strainer.
5. Excessive refrigerant.
6. Faulty outdoor high pressure sensor.
7. Faulty outdoor unit PCB.
Содержание WHSD24BE51
Страница 10: ...10 4 Location of Controls and Components 4 1 Indoor Unit 4 1 1 Location of Control ...
Страница 11: ...11 ...
Страница 12: ...12 4 1 2 Main Components 4 2 Outdoor Unit ...
Страница 13: ...13 5 Dimensions 5 1 Indoor Unit ...
Страница 14: ...14 5 2 Outdoor Unit ...
Страница 16: ...16 7 Block Diagram ...
Страница 17: ...17 8 Wiring Connection Diagram 8 1 Indoor Unit ...
Страница 18: ...18 8 2 Outdoor Unit ...
Страница 19: ...19 9 Electronic Circuit Diagram 9 1 Indoor Unit ...
Страница 20: ...20 9 2 Outdoor Unit ...
Страница 21: ...21 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board ...
Страница 22: ...22 10 2 Outdoor Unit 10 2 1 Main Printed Circuit Board ...
Страница 23: ...23 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 71: ...71 17 3 To Remove Pressure Gauge 17 4 To Remove Control Panel ...
Страница 72: ...72 17 5 To Remove Electronic Controller Board and Transformer 17 6 To Remove RCCB ...
Страница 74: ...74 When reinstall the water pipe use grease or water at the joining ...
Страница 79: ...79 18 3 Hydraulic Pump Performance ...
Страница 82: ...82 19 2 WH UD24BE5 1 WH UD30BE5 1 ...
Страница 83: ...83 ...