1. Safety Precautions 

  Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. 

  Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating and main 

circuit for the model installed. 

  The caution items stated here must be followed because these important contents are related to safety. The 

meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction 
will cause harm or damage, and the seriousness is classified by the following indications. 

 

 

This indication shows the possibility of causing death or serious injury. 

 

This indication shows the possibility of causing injury or damage to properties. 

 

  The items to be followed are classified by the symbols: 

 

 

  Carry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, 

care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for 
future reference. 

 

 

1.   Do not modify the machine, part, material during repairing service. 

2.   If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit. 

3.   Do not wrench the fasten terminal. Pull it out or insert it straightly. 

4.   Engage dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water leakage, 
      electrical shock or fire. 

5.   Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire. 

6.   Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, 
      refrigerant leakage, fire or electrical shock. 

7.   Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done,
      the set will drop and cause injury. 
8.   Do not install outdoor unit near handrail of veranda. When installing outdoor unit at veranda of high rise building, child may climb up  
      to outdoor unit and cross over the handrail and causing accident. 

9.   For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet
      must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire. 

10. This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. 
      Otherwise, it may cause electric shock in case equipment breakdown or insulation breakdown. 
11. Do not use joint cable for indoor/outdoor connection cable. Use specified indoor/outdoor connection cable, refer to Installation Instructions 
      CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force
      will be acted on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection. 
12. When install or relocate Air to Water Heatpump indoor/outdoor unit, do not let any substance other than the specified refrigerant, eg. air etc.
      mix into refrigerant cycle (piping). Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc. 
13. This is a R410A model, when connecting the piping, do not use any existing (R22) pipes and flare nuts. Using such same may cause 
      abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. Use only R410A refrigerant. 
      Thickness of copper pipes used with R410A must be more than 0.8 mm. Never use copper pipes thinner than 0.8 mm. 
      It is desirable that the amount of residual oil is less than 40 mg/10 m. 
14. During installation, install the refrigerant piping properly before run the compressor. Operation of compressor without fixing refrigeration piping
      and valves at opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion, injury etc. 
15. During pump down operation, stop the compressor before remove the refrigeration piping. Removal of refrigeration piping while compressor is
      operating and valves are opened condition will cause suck-in of air, abnormal high pressure in refrigeration cycle and result in explosion,  
      injury  etc. 
16. After completion of the installation servicing confirm there is no leakage of refrigerant gas. It may generate toxic gas when the refrigerant 
      contacts with fire. 

17. Ventilate the room if there is refrigerant gas leakage during operation. Extinguish all fire sources if present. It may cause toxic gas when the 
      refrigerant contacts with fire. 

18. Only use the supplied or specified installation parts, else, it may cause unit vibrate loose, water/refrigerant leakage, electrical shock or fire. 

 

 

This symbol denotes item that is PROHIBITED from doing. 

Содержание WH-SXC12F9E8

Страница 1: ...cuit WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potential dangers in attempting to service a product Products powered by electricity should be serviced or repaired only by experienced professional technicians Any attempt to serv...

Страница 2: ...ctrical circuit capacity is not enough or defect found in electrical work it will cause electrical shock or fire 10 This equipment must be properly earthed Earth line must not be connected to gas pipe water pipe earth of lightning rod and telephone Otherwise it may cause electric shock in case equipment breakdown or insulation breakdown 11 Do not use joint cable for indoor outdoor connection cable...

Страница 3: ...m fin It may cause injury 5 Select an installation location which is easy for maintenance 6 Pb free solder has a higher melting point than standard solder typically the melting point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high...

Страница 4: ...geration Oil cm 3 FV50S 1200 Refrigerant R410A kg oz 2 85 100 6 Height mm inch 1340 52 3 4 Width mm inch 900 35 7 16 Dimension Depth mm inch 320 12 19 32 Net Weight kg lbs 109 240 Liquid mm inch 9 52 3 8 Pipe Diameter Gas mm inch 15 88 5 8 Standard Length m ft 7 23 0 Pipe Length Range m ft 3 9 8 30 98 4 I D O D Height Difference m ft 20 65 6 Additional Gas Amount g m oz ft 50 0 5 Refrigeration Cha...

Страница 5: ...it Indoor Unit Performance Test Condition EN 14511 Outdoor Ambient C Cooling 16 43 Heating 20 35 Operation Range Water Outlet C Cooling 5 20 Heating 25 55 Internal Pressure Differential kPa Cooling 23 1 Heating 33 0 Condition Ambient Water A35W7 A7W35 A2W35 dB A Cooling 33 Cooling 33 Noise Level Power Level dB Cooling 46 Cooling 46 Height mm inch 892 35 1 8 Width mm inch 502 19 3 4 Dimension Depth...

Страница 6: ...ulb with controlled indoor water inlet temperature of 12 C and water outlet temperature of 7 C Heating capacities are based on outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet Bulb 42 8 F Wet Bulb with controlled indoor water inlet temperature of 30 C and water outlet temperature of 35 C Specification are subjected to change without prior notice for further improvement ...

Страница 7: ...ete function Weekly timer setting A class energy efficiency pump Water pump speed can be set by selection at control panel Improved deice cycle Protection Feature Random auto restart after power failure for safety restart operation Gas leakage protection Prevent compressor reverse cycle Inner protector to protect compressor Serviceability Feature Breakdown Self Diagnosis function System Status Che...

Страница 8: ...Water Outlet Gas Refrigerant Liquid Refrigerant Water drainage Water inlet Only applicable for WH S 09 12 14 16 9E8 Cabinet front plate Cabinet Handle 2 pieces Overload protector 4 pieces Heater assembly Expansion vessel Bushing Air purge valve d c e b a 15 2 6 5 1 7 8 1 8 2 16 12 14 13 1 2 3 4 5 a b c d e 6 7 9 10 11 12 13 14 15 16 8 1 8 2 4 3 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet ...

Страница 9: ... 155 97 157 171 57 Relative position between the indoor unit and the installation plate Front View Top View Front View Side View Bottom View 502 116 496 353 360 17 41 4 2 6 74 9 110 5 6 4 0 140 7 306 4 140 7 63 63 213 5 213 5 490 52 5 Installation Plate 6 6 Indoor unit external dimensions line 3 1 5 H O L E Unit mm ...

Страница 10: ...25 5 2 Outdoor Unit Unit mm Top View Front View Side View 900 400 320 355 900 318 5 253 210 165 243 1340 615 320 40 40 20 110 356 5 Side view Back view 30 ...

Страница 11: ...ainer Strainer 4 Way Valve Gas Side 3 Way Valve Liquid Side 3 Way Valve 2 Way Valve Accumulator in out Pressure Switch High Pressure Sensor Compressor Discharge Temp Sensor Compressor Tank Temp Sensor Compressor Water Pressure Gauge Capillary Tube Strainer Subcooler Expansion Valve Bypass Muffler Expansion Valve Piping size Model Gas Liquid Rated Length m Max Elevation m Min Piping Length m Max Pi...

Страница 12: ...SOLAR 3 WAY VALVE N SIGNAL DETECTION CIRCUIT NOISE FILTER CIRCUIT SW201 GROUNDING LA1 LA2 LA3 N SURGE PROTECTION CIRCUIT RCCB BL BL BL GR 400V 25A l n 30mA GROUNDING TERMINAL BOARD BACKUP HEATER POWER SUPPLY 2 3 phase AC400V 50Hz LB1 LB2 LB3 N OLP 80 3 C BR 2 BR OLP 80 3 C O O OLP 80 3 C 3 3 2 1 1 2 3 4 1 2 3 4 1 W W W R BL R O Y BR B W A FUSE2 20A 500V SIGNAL DETECTION CIRCUIT B B OLP 80 3 C 1 2 ...

Страница 13: ... V W P N 1 4 7 4 7 U 1 HIGH PRESSURE SWITCH R R ELECTRO MAGNETIC COIL BYPASS EXPANSION VALVE 1 1 ELECTRO MAGNETIC COIL MAIN EXPANSION VALVE DISCHARGE TEMP SENSOR THERMISTOR 6 2 6 W 1 1 2 CN TH2 BLUE CN TH3 BLACK CN EV1 WHITE CN EV2 YELLOW CN FM1 WHITE CN FM2 RED CN PSW1 BLUE 1 1 2 4 CN TH1 WHITE 1 4 LOWER FAN MOTOR UPPER FAN MOTOR 3 ELECTRONIC CONTROLLER MAIN ELECTRONIC CONTROLLER NF ELECTRO MAGNE...

Страница 14: ...ET button 3 Press SELECT button then press button to change SPEED and press SET to confirm 4 Press OFF ON button to quit setting EXTERNAL STATIC PRESSURE kPa WATER FLOW RATE I min P Q 0 0 0 10 20 30 40 50 10 0 20 0 30 0 40 0 50 0 60 0 70 0 80 0 90 0 100 0 110 0 1 2 3 4 5 6 7 14 6 Expansion Vessel Pre Pressure Checking Expansion Vessel with 10 L air capacity and initial pressure of 1 bar is install...

Страница 15: ... C DBT 6 C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7 m Outdoor Temperature C Outdoor Temperature C Input Power kW Outdoor Temperature C Capacity kW 1 000 2 000 3 000 4 000 5 000 6 000 15 11 7 3 1 5 9 13 17 21 25 10 000 11 000 12 000 13 000 14 000 15 000 15 11 7 3 1 5 9 13 17 21 25 ...

Страница 16: ... DBT C WBT Indoor water inlet temperature 12 C Indoor water outlet temperature 7 C Piping length 7 m Outdoor Temperature C Capacity kW Outdoor Temperature C Input Power kW 0 500 1 500 2 500 3 500 4 500 5 500 18 21 24 27 30 33 36 39 42 45 6 000 7 000 8 000 9 000 10 000 11 000 18 21 24 27 30 33 36 39 42 45 ...

Страница 17: ...C WBT Indoor water inlet temperature 30 C Indoor water outlet temperature 35 C Piping length 7 m Piping Length m Piping Length m Input Power kW Piping Length m Capacity kW 8 000 9 000 10 000 11 000 12 000 13 000 3 6 9 12 15 18 21 24 27 30 1 500 2 000 2 500 3 000 3 500 4 000 3 6 9 12 15 18 21 24 27 30 ...

Страница 18: ...35 C DBT C WBT Indoor water inlet temperature 12 C Indoor water outlet temperature 7 C Piping length 7 m Piping Length m Capacity kW Piping Length m Input Power kW 3 300 3 400 3 500 3 600 3 700 3 800 3 6 9 12 15 18 21 24 27 30 6 000 7 000 8 000 9 000 10 000 11 000 3 6 9 12 15 18 21 24 27 30 ...

Страница 19: ...670 18 2 2 WH UX12FE8 Water Out C 30 35 40 45 50 55 Outdoor Air C Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W Capacity W Input Power W 15 12000 4750 12000 4960 12000 5410 12000 5860 11800 6240 11600 6620 7 12000 3850 12000 4410 12000 4980 12000 5540 12000 5900 12000 6260 2 12000 3190 12000 3490 12000 3870 12000 4250 1...