5
2. Specifications
2.1 WH-MXC09G3E8
Item
Unit
Refrigerant System
Performance Test Condition
EN14511
Cooling Condition (Ambient/Water)
A35W7
-
Cooling Capacity
kW
7.00
-
BTU/h
23900
-
kcal/h
6020
-
EER
W/W
3.17
-
kcal/hW
2.72
-
Heating Condition (Ambient/Water)
A7W35
A2W35
Heating Capacity
kW
9.00
9.00
BTU/h
30700
30700
kcal/h
7740
7740
COP
W/W
4.84
3.59
kcal/hW
4.16
3.08
Air Flow
m
3
/min (ft
3
/min)
Cooling: 89.5 (3160)
Heating: 76.8 (2710)
Refrigeration Control Device
Expansion Valve
Refrigeration Oil
cm
3
FV50S (1200)
Refrigerant (R410A)
kg (oz)
2.30 (81.2)
Compressor
Type
Hermetic Motor (Rotary)
Motor Type
Brushless (4-poles)
Rated Output
kW
4.30
Fan
Type
Propeller Fan
Material
PP
Motor Type
DC (8-poles)
Input Power
W
-
Output Power
W
60
Fan Speed
rpm
Cooling: 540 (Top Fan) 580 (Bottom Fan)
Heating: 490 (Top Fan) 530 (Bottom Fan)
Heat Exchanger
Fin material
Aluminium (Pre Coat)
Fin Type
Corrugated Fin
Row × Stage × FPI
2 × 51 × 18
Size (W × H × L)
mm
903.7 × 1295.4 × 38.1
Item
Unit
Mono bloc Unit
Dimension
Height
mm (inch)
1410 (55-1/2)
Width
mm (inch)
1283 (50-1/2)
Depth
mm (inch)
320 (12-19/32)
Net Weight
kg (lbs)
155 (342)
Noise Level
dB-A
Cooling: 49
Heating: 49
Cooling: -
Heating: -
Power Level dB
Cooling: 67
Heating: 66
Cooling: -
Heating: -
Power Source (Phase, Voltage, Cycle)
ø
Three
V
400
Hz
50