6
Item
Unit
Mono bloc Unit
Input Power
kW
Cooling: 2.21
Heating: 1.86
Cooling: -
Heating: 2.51
Maximum Input Power For Mono bloc Unit
kW
5.41
Power Supply 1: Phase (ø) / Max. Current (A) / Max. Input Power (W)
Single / 25.0 / 5.41k
Power Supply 2: Phase (ø) / Max. Current (A) / Max. Input Power (W)
Single / 13.0 / 3.00k
Power Supply 3: Phase (ø) / Max. Current (A) / Max. Input Power (W)
- / - / -
Starting Current
A
10.2
Running Current
A
Cooling: 10.2
Heating: 8.6
Cooling: -
Heating: 11.6
Maximum Current For Mono bloc Unit
A
25.0
Power Factor
%
Cooling: 94
Heating: 94
Cooling: -
Heating: 94
Power factor means total figure of compressor and outdoor fan motor.
Power Cord
Number of core
-
Length m
(ft)
-
Thermostat
Electronic
Control
Protection Device
Electronic Control
Item
Unit
Water System
Performance Test Condition
EN14511
Operation Range
Outdoor Ambient
°C
Cooling: 16 ~ 43
Heating: -20 ~ 35
Water
Outlet
°C
Cooling: 5 ~ 20
Heating: 25 ~ 55
Internal Pressure Differential
kPa
Cooling: 14.3
Heating: 22.8
Water Pipe Diameter
Inlet
mm (inch)
30 (1-3/16)
Outlet
mm (inch)
30 (1-3/16)
Water Drain Hose Inner Diameter
mm (inch)
15.00 (19/32)
Pump
Motor Type
DC Motor
No. of Speed
7 (software selection)
Input
Power
W
50
Hot Water Coil
Type
Brazed Plate
No. of Plates
36
Size (H × W × L)
mm
65 × 120 × 376
Water Flow Rate
l/min (m
3
/h)
Cooling: 20.1 (1.2)
Heating: 25.8 (1.5)
Pressure Relief Valve Water Circuit
kPa
Open: 300, Close: 265 and below
Flow Switch
Magnetic Lead Switch
Protection Device
A
Residual Current Circuit Breaker (30)
Expansion Vessel
Volume
I
10
MWP
bar
3
Capacity of Integrated Electric Heater
kW
3.00
Note:
1.
Cooling capacities are based on outdoor air temperature of 35°C Dry Bulb with controlled water inlet temperature of 12°C and water outlet
temperature of 7°C.
2.
Heating capacities are based on outdoor air temperature of 7°C Dry Bulb (44.6°F Dry Bulb), 6°C Wet Bulb (42.8°F Wet Bulb) with controlled
water inlet temperature of 30°C and water outlet temperature of 35°C.
3.
Specifications are subjected to change without prior notice for further improvement.