63
12.4 Flow
Switch
12.4.1 Flow Switch Control
1 The water flow switch serve as an overload protector that shuts down the unit when the water level is
detected to be low.
2 Detection is Lo (0V) when there is no water flow, and detection is Hi (5V) when there is water flow.
12.5 Force Heater Mode Operation
The backup heater also serves as backup in case of malfunctioning of the Mono bloc unit.
1 Make sure the OFF/ON control panel LED is OFF (no operation).
2 Press the Force button to start the force heater mode operation.
3 During force heater mode, all other operations are not allowed.
4 Press OFF/ON button to stop the force heater mode operation.
12.6 Mono Bloc Unit Safety
12.6.1 Mono Bloc Unit Safety Control
1 When water pump is ON, the system will start checking flow switch status (ON/OFF).
2 If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds.
If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal
mode.
If the water inlet temperature exceeds 80°C for continuously 10 seconds, the water pump will be OFF
immediately.
3 After water pump OFF for more than 10 minutes, it will be ON back and the Mono bloc unit safety control
checking is restarted.
12.7 Auto
Restart
Control
1 When the power supply is cut off during the operation of Mono bloc unit, the compressor will re-operate after
power supply resumes.
Содержание WH-MDC09C3E8
Страница 15: ...15 4 Location of Controls and Components 4 1 Mono Bloc Unit ...
Страница 18: ...18 ...
Страница 19: ...19 ...
Страница 20: ...20 4 1 2 2 Weekly Timer Setting ...
Страница 21: ...21 4 1 2 3 Setting Up the Special Functions ...
Страница 22: ...22 5 Dimensions 5 1 Mono Bloc Unit ...
Страница 23: ...23 6 Refrigeration And Water Cycle Diagram ...
Страница 24: ...24 ...
Страница 25: ...25 7 Block Diagram 7 1 WH MDC09C3E8 WH MDC09C3E8 1 ...
Страница 26: ...26 7 2 WH MDC12C9E8 WH MDC14C9E8 WH MDC16C9E8 WH MDC12C9E8 1 WH MDC14C9E8 1 WH MDC16C9E8 1 ...
Страница 27: ...27 8 Wiring Connection Diagram 8 1 WH MDC09C3E8 WH MDC09C3E8 1 ...
Страница 28: ...28 ...
Страница 29: ...29 8 2 WH MDC12C9E8 WH MDC14C9E8 WH MDC16C9E8 WH MDC12C9E8 1 WH MDC14C9E8 1 WH MDC16C9E8 1 ...
Страница 30: ...30 ...
Страница 31: ...31 9 Electronic Circuit Diagram 9 1 WH MDC09C3E8 WH MDC09C3E8 1 ...
Страница 32: ...32 ...
Страница 33: ...33 9 2 WH MDC12C9E8 WH MDC14C9E8 WH MDC16C9E8 WH MDC12C9E8 1 WH MDC14C9E8 1 WH MDC16C9E8 1 ...
Страница 34: ...34 ...
Страница 35: ...35 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 36: ...36 10 1 2 Solar Printed Circuit Board Optional ...
Страница 37: ...37 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 38: ...38 10 2 2 Noise Filter Printed Circuit Board ...
Страница 39: ...39 11 Installation Instruction Mono Bloc Unit Dimension Diagram ...
Страница 40: ...40 Main Components ...
Страница 52: ...52 ...
Страница 58: ...58 ...
Страница 59: ...59 ...
Страница 69: ...69 Heat Tank Mode Heating Priority Set Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 118: ...118 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 121: ...121 17 10To Remove Bottle Complete When reinstall the water pipe use grease or water at the joining ...
Страница 133: ...133 ...