9
WIRE STRIPPING AND CONNECTING REQUIREMENT
ACCEPT
PROHIBITED
Conductor
over insert
Conductor not
fully insert
Conductor
fully insert
PROHIBITED
Wire stripping
No loose strand
when insert
5mm or more
(gap between wires)
Indoor/outdoor
connecting
terminal board
10 ± 1mm
•
Make sure all the piping installations are properly done before carry
out below steps.
CHARGE THE WATER
For Domestic Hot Water Tank
1. Set the Domestic Hot Water Tank Discharge (Drain Tap)
g
to “CLOSE”.
“CLOSE”
“OPEN”
Domestic Hot Water Tank Discharge (Drain Tap)
g
2. Set all Tap / Shower “OPEN”.
3. Start fi lling water to the Domestic Hot Water Tank via Tube Connector
i
.
After 20~40min, water should fl ow out from Tap / Shower.
Else, please contact your local authorized dealer.
4. Check and make sure no water leaking at the tube connecting points.
5. Set the Domestic Hot Water Tank Discharge (Drain Tap)
g
to
“OPEN” for 10 seconds to release air from this pipeline. Then set
it “CLOSE”.
6. Turn the Safety Relief Valve
o
knob counterclockwise slightly and
hold for 10 seconds to release air from this pipeline. Then recover
the knob to original position.
7. Ensure Step 5 & 6 is carried out each time after charging water to
Domestic Hot Water Tank.
8. To prevent back pressure from happening to the Safety Relief
Valve
o
, do turn the Safety Relief Valve
o
knob counterclockwise.
For Space Heating / Cooling
1. Turn the plug on the Air Purge Valve
d
outlet anticlockwise by one
complete turn from fully closed position.
Air purge valve
d
Plug (turn
anticlockwise by
one complete turn)
2. Set the Pressure Relief Valve
e
lever “DOWN”.
Pressure relief valve
e
Pressure relief valve
e
Lever
Turn down
or
Pressure relief valve
e
Lever
Turn down
Pressure relief valve
e
3. Start fi lling water (with pressure more than 0.1 MPa (1 bar)) to the
Space Heating / Cooling circuit via Tube Connector
a
. Stop fi lling water
if the free water fl ow through Pressure Relief Valve
e
discharge hose.
4. Turn ON the Tank Unit and make sure Water Pump
4
is running.
5. Check and make sure no water leaking at the tube connecting points.
6. The water may drip from this discharge hose. Therefore must guide
the hose without close or block the outlet of the hose.
CHARGING AND
DISCHARGING THE WATER
5
2. An isolating device must be connected to the power supply cable.
•
Isolating device (disconnecting means) should have minimum
3.0 mm contact gap.
•
Connect the approved polychloroprene sheathed power
supply 1 cord and power supply 2 cord and type designation
60245 IEC 57 or heavier cord to the terminal board, and to the
other end of the cord to isolating device (Disconnecting means).
See below table for cable size requirement.
Model
Power
Supply
Cord
Cable Size
Isolating
Devices
Recommended
RCD
Tank Unit
Outdoor Unit
WH-ADC0309K3E5
WH-ADC0309K3E5AN
WH-UDZ03KE5*,
WH-UDZ05KE5*
1
3 x min 1.5 mm
2
15/16A
30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A
30mA, 2P, type AC
WH-UDZ07KE5*,
WH-UDZ09KE5*
1
3 x min 2.5 mm
2
25A
30mA, 2P, type A
2
3 x min 1.5 mm
2
15/16A
30mA, 2P, type AC
WH-ADC0309K6E5
WH-ADC0309K6E5AN
WH-UDZ03KE5*,
WH-UDZ05KE5*
1
3 x min 1.5 mm
2
15/16A
30mA, 2P, type A
2
3 x min 4.0 mm
2
30A
30mA, 2P, type AC
WH-UDZ07KE5*,
WH-UDZ09KE5*
1
3 x min 2.5 mm
2
25A
30mA, 2P, type A
2
3 x min 4.0 mm
2
30A
30mA, 2P, type AC
3. To avoid the cable and cord being damaged by sharp edges, the
cable and cord must be passed through a bushing (located at the
bottom of Control Board
6
) before terminal board. The bushing
must be used and must not be removed.
Terminals on the Outdoor Unit
1
2
3
Colour of wires (Connecting cables)
Terminals on the Tank unit
L
N
L
1
N
1
1
2
3
(Power Supply Cord)
Terminals on the isolating devices
from power supply (Disconnecting
means)
L
N
L
1
N
1
Power Supply 1 Power Supply 2
Tank Unit/
Outdoor Unit
connection
Power Supply 2 Cable
Power Supply 1 Cable
Terminal
Board
RCCB/ELCB
*1
*1
Connecting Cable
Holder
(Clamper)
Holder
(Clamper)
Terminal screw
Tightening torque cN•m {k
g
f•cm}
M4
157~196 {16~20}
M5
196~245 {20~25}
*1 - Earth wire must be longer than other cables for safety reasons
CONNECTING REQUIREMENT
For Tank Unit WH-ADC0309K3E5, WH-ADC0309K3E5AN with
WH-UDZ03KE5*, WH-UDZ05KE5*, WH-UDZ07KE5*, WH-UDZ09KE5*
•
The equipment’s Power Supply 1 complies with IEC/EN 61000-3-2.
•
The equipment’s Power Supply 1 complies with IEC/EN 61000-3-3 and
can be connected to current supply network.
•
The equipment’s Power Supply 2 complies with IEC/EN 61000-3-2.
•
The equipment’s Power Supply 2 complies with IEC/EN 61000-3-3 and
can be connected to current supply network.
For Tank Unit WH-ADC0309K6E5, WH-ADC0309K6E5AN with
WH-UDZ03KE5*, WH-UDZ05KE5*, WH-UDZ07KE5*, WH-UDZ09KE5*
•
The equipment’s Power Supply 1 complies with IEC/EN 61000-3-2.
•
The equipment’s Power Supply 1 complies with IEC/EN 61000-3-3 and
can be connected to current supply network.
•
The equipment’s Power Supply 2 complies with IEC/EN 61000-3-12.
•
The equipment’s Power Supply 2 complies with IEC/EN 61000-3-11
and shall be connected to suitable supply network, with the following
maximum permissible system impedance Z
max
= 0.123 ohm (
) at the
interface. Please liaise with supply authority to ensure that the Power
Supply 2 is connected only to a supply of that impedance or less.