Panasonic Electric Works Nordic AB
MEW01228 Rev: 1
Operating Instructions Web512 V2.6.x for Web-server II 1598
32
4.10
Operation; Maintenance
NOTE!
Log in on User level 2, 3 or 4 is required.
The
Daily - Disablement
view is default (
User level 2
). See page 27.
The
Maintenance - Disablement
view. (
User level 3
). See below.
The
Service
–
Misc.
view. (
User level 4
). See page 35.
Click
Menu
to get access to the following buttons:
If required, click
Login
and Log in on User level 3 or 4.
Click
Maintenance
to open the
Maintenance - Disablement
view.
4.10.1
Maintenance
–
Disablement
The
Maintenance - Disablement
view:
4.10.1.1
Control Unit Loop
Like menu H8/S2 & S3.
A specified COM
Loop
(0-3) in a specified
Control Unit
(00-29) can
be disabled / re-enabled.
4.10.1.2
BS4 Loop
Like menu H8/S2 & S3.
A specified BS4
Loop
(0-3) on a specified expansion board 1584,
Autronica interface
Board
(0-3), in a specified
Control Unit
(00-29),
can be disabled / re-enabled.
4.10.1.3
DET8 Loop (Zone line input)
Like menu H8/S2 & S3.
A specified zone line input,
Loop
(0-7) on a specified expansion
board 1580, 8 zones expansion
Board
(0-5), in a specified
Control
Unit
(00-29), can be disabled / re-enabled.
4.10.1.4
Loop unit Loop (Loop unit zone line input)
Like menu H8/S2 & S3.