PACD011001G2 / PACD011004G3
Bad Examples and Good Examples in Installation
Urban Multi Inverter “MX1” Series
77
7.7
Example 7:
Transmission wiring between the cool/heat selector and the
outdoor unit is too close to a high voltage wire
.
Situation
Heating is indicated despite having selected cooling with the cool/heat selector.
Cause and
Remedial Action
The transmission wiring between the cool/heat selector and the outdoor unit is too close to a high voltage
wire. An induced voltage is, therefore, being impressed on the transmission wiring which is causing a
heating/cooling malfunction in the outdoor unit PC board.
Bypassing the transmission wiring will allow the unit to function normally.
Main Points
Keep low and high voltage wiring away from each another.