6. AIR PURGING
Air and moisture in the refrigerant system may have
undesirable effects as indicated below.
●
pressure in the system rises
●
operating current rises
●
cooling (or heating) efficiency drops
●
moisture in the refrigerant circuit may freeze and
block capillary tubing
●
water may lead to corrosion of parts in the refrigerant
system
Therefore, the indoor unit and tubing between the
indoor and outdoor unit must be leak tested and
evacuated to remove any noncondensables and
moisture from the system.
■
Air Purging with a Vacuum Pump (for Test Run)
Preparation
Check that each tube between the indoor and outdoor
units have been properly connected and all wiring for
the test run has been completed. Remove the valve
caps from all service ports on the outdoor unit. (Fig.
6-2) Note that all service valves on the outdoor unit are
kept closed at this stage.
The balance tube leak test is not necessary if only 1
outdoor unit is installed.
Leak test
(1) Attach a manifold valve (with pressure gauges) and
dry nitrogen gas cylinder to all service ports with
charge hoses.
The balance tube leak test is not necessary if only 1
outdoor unit is installed.
(2) Pressurize the system to no more than 512 psig
(36 kgf/cm
2
G) with dry nitrogen gas and close the
cylinder valve when the gauge reading reaches
512 psig (36 kgf/cm
2
G). Then, test for leaks with
liquid soap.
Manifold gauge
Outlet
Inlet
Vacuum pump
Manifold valve
Pressure
gauge
Lo
Hi
Charge hose
Outdoor unit
Close
Open
Discharge
tube
Suction
tube
Liquid
tube
Nitrogen gas cylinder
(In vertical standing
position)
Close
Close
Open
Balance
tube
Open
Close
Open
Cylinder
valve
Use a manifold valve for air
purging. If it is not available,
use a stop valve for this
purpose. The “Hi” knob of
the manifold valve must
always be kept closed.
CAUTION
CAUTION
To avoid nitrogen entering the
refrigerant system in a liquid
state, the top of the cylinder
must be higher than the
bottom when you pressurize
the system. Usually, the
cylinder is used in a vertical
standing position.
Valve cap
Service port cap
Flare nut
W-3WAY̲ECO-i̲U.indb 36
W-3WAY̲ECO-i̲U.indb 36
2011/11/07 16:29:38
2011/11/07 16:29:38
Содержание U-72MF1U9
Страница 53: ...53 W 3WAY ECO i U indb 53 W 3WAY ECO i U indb 53 2011 11 07 16 29 45 2011 11 07 16 29 45...
Страница 54: ...54 W 3WAY ECO i U indb 54 W 3WAY ECO i U indb 54 2011 11 07 16 29 45 2011 11 07 16 29 45...
Страница 55: ...55 W 3WAY ECO i U indb 55 W 3WAY ECO i U indb 55 2011 11 07 16 29 45 2011 11 07 16 29 45...