Mini VRF SYSTEM
Trouble Diagnosis
6
3. Mini VRF Alarm Codes
F06 Alarm
Alarm code
F06
Alarm meaning
Outdoor unit heat exchanger gas temperature sensor has failure. (EXG)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less)
(2) Open circuit (A/D step is 1014 steps or more)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—
F07 Alarm
Alarm code
F07
Alarm meaning
Outdoor unit heat exchanger liquid temperature sensor has failure. (EXL)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less)
(2) Open circuit (A/D step is 1014 steps or more)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—
F08 Alarm
Alarm code
F08
Alarm meaning
Outdoor temperature sensor has failure. (TO)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less)
(2) Open circuit (A/D step is 1014 steps or more)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—
F12, F14 Alarm
Alarm code
F12, F14
Alarm meaning
F12 : Compressor inlet temperature sensor has failure. (SCT)
F14 : Subcooling heat exchanger temperature sensor has failure. (SCG)
Alarm conditions
(1) Short circuit (A/D step is 10 steps or less)
(2) Open circuit (A/D step is 1014 steps or more)
Probable cause
(1) Sensor malfunction (including connector)
(2) The Outdoor Unit Control PCB malfunction
Check
(1) Measure the sensor resistance. Check that the sensor is operating normally.
(2) Use a remote controller monitor or PC monitor to check the temperature that is recognized by
the microcomputer.
Correction
—
Example
—
Notes
—
SM830258-01_欧州向け_1fan_mini_VRF.indb 9
18/03/13 17:29:22