Obtain charge amount for each tubing size
Note that the charge amounts per 3.3 ft. are different for each liquid tubing size.
ø3/8" (ø9.52)
→
LA + LB + LC + LD
: 212 ft.
×
0.602 oz/ft. = 127 oz
ø1/4" (ø6.35)
→
1 + 2 + 3 + 4 + 5 : 75 ft.
×
0.279 oz/ft.
=
20 oz
Total
147 oz
Additional refrigerant charge amount is 147 oz.
Be sure to check the limit
density for the room in which
the indoor unit is installed.
CAUTION
●
Example of each tubing length
Main tubing
Distribution joint tubing
LA = 131 ft.
Indoor side
LB = 16 ft.
1 = 16 ft.
4 = 20 ft.
LC = 16 ft.
2 = 16 ft.
5 = 16 ft.
LD = 49 ft.
3 = 7 ft.