Panasonic U-16GE2E5 Скачать руководство пользователя страница 7

EN - 7

EN

3-WAY Multi Models
Table 2-1 Refrigerant tubing length and range of rise/fall

Indoor unit

45.0 kW

56.0 kW

71.0 kW

Capacity proportion of the indoor units to the outdoor unit

50 - 200 %

Minimum capacity of indoor units that can be connected 

 22 type (equivalent to 0.8 horsepower)

Maximum number of indoor units (systems) that can be connected

24

Maximum allowable tubing length (L)

L

1

 120 m (equivalent length 

 145 m) 

(*1)

Difference between longest and shortest tubing lengths after the 
No. 1 branch (

fi

 rst branching point)

L

2

 - L

8

 30 m

Maximum length of each tube branch

1, 

2...

8

 30 m

Maximum allowable height difference 
between indoor and outdoor units

If outdoor unit is above

H

1

 50 m

If outdoor unit is below

H

2

≤ 

35 m 

(*2)

Maximum allowable height difference between indoor units

H

3

≤ 

15 m 

(*3)

Maximum length from the 

fi

 rst T-tee to the last T-tee

L

3

≤ 

2 m

(*1) The minimum length of tubes between outdoor units and indoor units is 7 m.
(*2) If cooling mode is expected to be used when the external temperature is 10°C or below, install so the 

maximum length is 30 m.

(*3) Install so that the height difference between indoor units after the 

fi

 nal branch is within the limits shown in 

Fig 3.

D1

H1

D2

D3

Dn

d21

d22

d24

d23

L5

L4

d4

d3

d2

d5

d1

Solenoid valve kit (purchased separately)

Externally mounted solenoid valve kit (sold separately)

Branch tube (purchased separately)

Ball valve (purchased separately)

T-tee (provided by installer)

Closed (pinch) weld

Fig. 6 Length of Refrigerant Tubing

2-tube line (gas tube, liquid tube)

CAUTION : 1)  Each indoor unit requires a solenoid valve kit.
 

2)  Never branch the tube between a solenoid valve kit and indoor unit.

 

3)  Never branch the tube again after the header branching.

 

4)  If using an external electric valve kit, install it between the solenoid 

valve kit and the indoor unit.

Indoor unit

Solenoid 

valve kit

Indoor unit

Header (purchased separately)

Solenoid 

valve kit

Header

Maximum length of each 

branch tube

 30 m

First branch

(Branch line) 

L3 (Minimum length after 

fi

 rst 

branch)

H2 (Height difference between indoor units)

 15 m

Maximum allowable tubing length L1 

 120 m

L2 (Maximum length after 

fi

 rst branch)

Height difference between indoor units after the 

fi

 nal branch must be less than 4 m.

If height difference between indoor units after the 

fi

 nal branch cannot be less than 4 m, 

divide the height difference between upper and lower units (2 to 1).

More than 4 m

X m

2X m or 

more

4 m or less

3-tube line (discharge gas tube, suction gas tube, liquid tube)

Outdoor unit

External electric 

valve kit

Maximum height differential of indoor units after 

fi

 nal branch

00-Installation̲All.indb   7

00-Installation̲All.indb   7

2012/09/07   9:32:39

2012/09/07   9:32:39

Содержание U-16GE2E5

Страница 1: ...ECTRICAL SHOCK CAN CAUSE S E V E R E P E R S O N A L I N J U RY OR DEATH ONLY A QUALIFIED EXPERIENCEDELECTRICIANSHOULD ATTEMPT TO WIRE THIS SYSTEM Do not supply power to the unit all wiring and tubing...

Страница 2: ...can produce dangerously toxic gas NOTICE The English text is the original instructions Other languages are translation of the original instructions SAFETY PRECAUTIONS Be sure to arrange installation f...

Страница 3: ...structure around the outdoor unit If such protections are not installed an injury from falling while working may result Be sure to stand on a stable surface when installing the outdoor unit on an ele...

Страница 4: ...the main tubing is level The openings can be set at any angle when the main tubing is vertical but be sure to curve a portion of the connected tubing upward Always close weld the end point of the T te...

Страница 5: ...tubing main tubing size 1 2 Outdoor tubing Main tubing Outdoor unit gross capacity kW 45 56 71 85 90 101 112 116 127 142 Gas tube mm 28 58 31 75 31 75 38 1 38 1 Liquid tube mm 12 7 15 88 15 88 19 05 1...

Страница 6: ...ndoor units A to B Unit type 22 28 36 45 56 71 80 90 112 140 160 224 280 Tube size Equivalent horsepower 0 8 1 1 3 1 6 2 2 5 3 3 2 4 5 6 8 10 Gas tube mm 12 7 15 88 22 22 25 4 Liquid tube mm 6 35 9 52...

Страница 7: ...valve kit purchased separately Externally mounted solenoid valve kit sold separately Branch tube purchased separately Ball valve purchased separately T tee provided by installer Closed pinch weld Fig...

Страница 8: ...8 Discharge tube 12 7 Liquid tube 9 52 Table 2 4 Solenoid valve kit indoor unit tubes 2 tube side Indoor unit Unit Type 22 56 kW 71 160 kW Equivalent Horsepower 0 8 2 0 2 5 6 0 Tubing size mm Gas tube...

Страница 9: ...els If this condition is not met the system must either be equipped with two of the countermeasures alarm ventilation or safety shut off valve or be redesigned Please note when the system is in the lo...

Страница 10: ...eps such as connecting the foundation and the building structure with reinforcing bars in accordance with building utilities earthquake resistant design and construction guidelines Foundation types A...

Страница 11: ...pressure or shock to the pipe path In particular take sufficient precautions when installing near roads There is a danger of fire or explosion resulting from fuel gas leakage In regions with heavy sn...

Страница 12: ...care that it is not blocked from bending smashing the exhaust drain hose If the exhaust drain hose is blocked it will result in poor engine combustion and may lead to an equipment breakdown Slope the...

Страница 13: ...r seamless tubing C1220T Tubing size Choose tubing sizes according to tables 1 2 1 3 1 5 and 2 2 to 2 4 Use tube with thickness as per Table 4 Table 4 Tubing size mm Exterior diameter Wall thickness T...

Страница 14: ...it before brazing Cool the tubes with wet cloths or other materials to prevent the value inside the machine from being damaged by the brazing heat Be sure to replace the contents of the tube with nit...

Страница 15: ...uffocation and injury to nearby persons Fig 18 Gas tube Liquid tube Pressure gauge Pressure reducing valve Siphon tube Nitrogen When checking for air vacuum tightness do so at all service ports at the...

Страница 16: ...ubing G total length in meters of 6 35 mm diameter liquid tubing H Unit additional charge amount Table 7 Be careful to charge accurately according to refrigerant weight Charging procedure Evacuate the...

Страница 17: ...tubes that is heat resistant to at least 120 C and at least 80 C for liquid and suction tubes tubes Use separate piping for the power cables and the control cables If the cables are passed through th...

Страница 18: ...should the engine need to be replaced Table 8 Engine external dimensions mm Package weight kg Width Depth Height 670 810 640 760 650 700 170 Figures in parentheses are the external dimensions of the w...

Страница 19: ...h outdoor unit be sure to install them on the vibration resistant frame Installation on the ground is prohibited When anchoring the refrigerant tubing always anchor the tubing at the main tubing to pr...

Страница 20: ...EN 20 NOTE 00 Installation All indb 20 00 Installation All indb 20 2012 09 07 9 32 42 2012 09 07 9 32 42...

Страница 21: ...icolo 7 1 delle regolamentazioni 842 EC 2006 NON DISPERDERE R410A NELL ATMOSFERA L R410A UN GAS FLUORATO CAUSA DI EFFETTO SERRA E COPERTO DAL PROTOCOLLO DI KYOTO CON UN POTENZIALE DI RISCALDAMENTO GLO...

Отзывы: