Fixing transmission wiring (See figure 23)

Inside switchbox

Outside unit

Sequential start

The outdoor unit PC board (A1P) is factory set at "Sequential start
available".

Setting the cool/heat operation 

1

Performing cool/heat setting with the remote controller
connected to the indoor unit.

Keep the cool/heat selector switch (DS1) on the outdoor unit PC
board at the factory setting position IN/D UNIT. (See figure 22)

2

Performing cool/heat setting with the cool/heat selector.

Connect the cool/heat selector remote controller (optional) to the
A/B/C terminals and set the cool/heat selector switch (DS1) on
the outdoor unit PC board (A1P) to OUT/D UNIT. (See figure 25)

8.8.

Field line connection: power wiring

The power cord must be clamped to the plastic bracket using field
supplied clamp material.

The green and yellow striped wrapped wires must be used for
grounding. (See figure 21)

1

Heating/cooling switching remote control cord (when a heating/
cooling switch remote control (optional) is connected) (ABC) (not 
for U-5~18MX4)

2

Fix to the indicated plastic brackets using field supplied clamping 
material.

3

Wiring between the units (Outdoor - outdoor) (F1+F2 right)

4

Wiring between the units (Indoor - outdoor) (F1+F2 left)

5

Wiring for multi connection (only for U-20~54MX4) (Q1+Q2)

6

Plastic bracket

Be sure to follow the limits below. If the unit-to-unit
cables are beyond these limits, it may result in
malfunction of transmission.

-

Maximum wiring length:

1000 m

-

Total wiring length:

2000 m

-

Maximum interunit wiring length 
between outdoor units:

30 m

-

Transmission wiring to cool/heat 
selector:

500 m

-

Maximum number of branches:

16

Maximum number of outdoor units connectable: 10.

Up to 16 branches are possible for unit-to unit cabling.
No branching is allowed after branching. 
(See figure 16)

Never connect the power supply to transmission
wiring terminal block. Otherwise the entire system
may break down.

Never connect 400 V to the terminal block of the
interconnecting wiring. Doing so will break the entire
system.
-

The wiring from the indoor units must be 
connected to the F1/F2 (In-Out) terminals on the 
PC board in the outdoor unit.

-

After installing the interconnecting wires inside the 
unit, wrap them along with the on-site refrigerant 
pipes using finishing tape, as shown in figure 12.

For the above wiring, always use vinyl cords with 0.75
to 1.25 mm

2

 sheath or cables (2-core wires). (3-core

wire cables are allowable for the cooler/heater
changeover remote controller only.)

1

Outdoor unit

2

Indoor unit

3

Main line

4

Branch line 1

5

Branch line 2

6

Branch line 3

7

No branch is allowed after branch

8

Central remote controller (etc...)

A

Transmission wiring between outdoor unit and indoor 
unit(s)

B

Transmission wiring between outdoor units

1

Liquid pipe

2

Gas pipe

3

Insulator

4

Interconnecting wiring

5

Finishing tape

Be sure to keep the power line and transmission line
apart from each other.

Be careful about polarity of the transmission line.

Make sure that the transmission line is clamped as
shown in figure 23.

Check that wiring lines do not make contact with
refrigerant piping.

Firmly close the lid and arrange the electrical wires so
as to prevent the lid or other parts from coming loose.

When you do not use a wire conduit, be sure to
protect the wires with vinyl tubes etc, to prevent the
edge of the knock-out hole from cutting the wires.

1

Remote controller

1

Cool/heat selector

For low-noise operation, it is necessary to get the optional
'External control adaptor for outdoor unit' (DTA104A61/62).

For details, see the installation manual attached to the
adaptor.

1

Power supply (400 V, 3 N~50 Hz)

2

Fuse

3

Earth leakage breaker

4

Grounding wire

5

Power supply terminal block

6

Connect each power wire
RED to L1, WHT to L2, BLK to L3 and BLU to N

7

Ground wire (GRN/YLW)

8

Clamp the power wire to the plastic bracket using a field supplied 
clamp to prevent external force being applied to the terminal. 

9

Clamp (field supply)

10

Cup washer

11

When connecting the earth wire, it is recommended to perform 
curling.

Do not allow the ground wires to contact the
compressor lead wires. If the wires contact each
other, adverse effects may occur to other units.

When connecting or disconnecting a power supply
cord, make sure that the current-carrying conductors
become taut before the earthing conductor.

Содержание U-10MX4XPQ

Страница 1: ... Multi airconditioner Nederlands Manual de instalación Acondicionador de aire Urban Multi Español Manuale d installazione Climatizzatore Urban Multi Italiano Á ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÏÈÌ ÙÈÛÙÈÎfi Urban Multi EÏÏËÓÈÎ Manual de instalação Ar condicionado Urban Multi Portugues U 5MX4XPQ U 8MX4XPQ U 10MX4XPQ U 12MX4XPQ U 14MX4XPQ U 16MX4XPQ U 18MX4XPQ INSTALLATION MANUAL URBAN MULTI AIR CONDITIONER ...

Страница 2: ...10 mm d 500 mm a 50 mm b 100 mm c 50 mm d 500 mm a 200 mm b 300 mm a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm a 200 mm b 300 mm e 400 mm A B C D A B 3 a 10 mm b 300 mm c 10 mm d 500 mm e 20 mm f 600 mm a 50 mm b 100 mm c 50 mm d 500 mm e 100 mm f 500 mm 4 a 10 mm b 300 mm c 10 mm d 300 mm e 20 mm f 500 mm a 50 mm b 100 mm c 50 mm d 100 mm e 100 mm f 500 mm...

Страница 3: ...NIT TO OUT D UNIT TO MULTI UNIT A1P 3 A B C F1 F2 F1 F2 Q1 Q2 Q1 Q2 A1P 4 4 5 6 2 1 3 Q1 Q2 7 1 2 1 2 5 3 4 1 6 6 2 2 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N 6 5 7 8 9 10 11 1 2 6 3 6 5 4 3 B A 1 max 15 B 1 120 mm 500 mm 1 1 1 A B 2 2 2 2 2 2 8 5 6 7 7 4 3 U 5 12MX4 U 14 18MX4 1 2 3 4 1 5 6 7 8 13 14 15 16 17 20 18 19 23 21 24 ...

Страница 4: ...o the installation manual supplied with these units for their installation 1 1 Combination The indoor units can be installed in the following range Always use appropriate indoor units compatible with R410A To learn which models of indoor units are compatible with R410A refer to the product catalogs Pay attention when connecting outdoor units in multi combination U MX3XPQ A units are NOT compatible...

Страница 5: ... 36MX4 U 18MX4 U 18MX4 450 1440 64 U 38MX4 U 18MX4 U 12MX4 U 12MX4 475 1235 61 U 40MX4 U 10MX4 U 12MX4 U 12MX4 500 1300 64 U 42MX4 U 12MX4 U 12MX4 U 12MX4 525 1365 64 U 44MX4 U 8MX4 U 18MX4 U 18MX4 550 1430 64 U 46MX4 U 10MX4 U 18MX4 U 18MX4 575 1495 64 U 48MX4 U 12MX4 U 18MX4 U 18MX4 600 1560 64 U 50MX4 U 14MX4 U 18MX4 U 18MX4 625 1625 64 U 52MX4 U 16MX4 U 18MX4 U 18MX4 650 1690 64 U 54MX4 U 18MX...

Страница 6: ...eak Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals Small animals making contact with electrical parts can cause malfunctions smoke or fire Please instruct the customer to keep the area around the unit clean If not the unit may fall over and cause damage or injury A B C D Sides along the installation site with obstacles Suc...

Страница 7: ...uately bears the weight of the unit NOTE Use filler cloth on the forklift arms to prevent damaging the unit If the paint on the bottom frame peels off the anti corrosion effect may decrease Do not use stands to only support the corners See figure 7 Model A B U 5MX4 635 497 U 8 10MX4 930 792 U 12 18MX4 1240 1102 X Not allowed except for U 5MX4 O Allowed units mm Prepare a water drainage channel aro...

Страница 8: ...outdoor and indoor units is 90 m or more the size of the main pipes both gas side and liquid side must be increased Depending on the length of the piping the capacity may drop but even in such a case it is possible to increase the size of the main pipes Refer to page 9 If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease 6 ...

Страница 9: ...ge 5 always referring to the installation manual delivered with the kit 4 2 Possible installation patterns and configurations The piping between the outdoor units must be routed level or slightly upward to avoid the risk of oil detention into the piping side Pattern 1 Pattern 2 Any gas remaining inside the stop valve may blow off the pinched piping causing damage or injury 1 Service port 2 Gas sid...

Страница 10: ... of straight section can be ensured Improper installation may lead to malfunction of the outdoor unit 6 Piping length restrictions Make sure to perform the piping installation within the range of the maximum allowable pipe length allowable level difference and allowable length after branching as indicated in 6 6 Example of connection on page 8 6 5 Protection against contamination when installing p...

Страница 11: ... select the line branch pipe When using line branch pipe at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the outdoor unit For line branch pipes other than the first branch select the proper branch kit model based on the total capacity index How to select the header branch pipe Choose from the following table in accordance wi...

Страница 12: ...size a b 2 c 2 d 2 e 2 f 2 g 2 h i j k l m n p 1000 m Indoor unit to the nearest branch kit 40 m h i j p 40 m The difference between the distance of the outdoor unit to the farthest indoor unit and the distance of the outdoor unit to the nearest indoor unit 40 m The farthest indoor unit 8 The nearest indoor unit 1 a b c d e f g p a h 40 m Note 2 If the pipe size above the refnet header is Ø34 9 or...

Страница 13: ...d side stop valve Gas side stop valve Performing the airtightness test and vacuum drying Valve A must always be shut Otherwise the refrigerant in the unit will pour out Close Open Open Close Close NOTE Make sure to perform airtightness test and vacuum drying using the service ports of the stop valves of the liquid side and of the gas side For the service port location refer to the Caution label at...

Страница 14: ...iting S1NPH Pressure sensor high S1NPL Pressure sensor low S1PH 3PH Pressure switch high T1A Current sensor A6P A7P SD1 Safety devices input V1R Power module A4P A8P V1R V2R Power module A3P X1A X4A Connector M1F M2F X1M Terminal strip power supply X1M Terminal strip control A1P X1M Terminal strip A5P Y1E 2E Expansion valve electronic type main subcool Y1S Solenoid valve hotgas bypass Y2S Solenoid...

Страница 15: ...ate normally in reversed phase If you connect in reversed phase replace two of the three phases This unit has a reverse phase detection circuit If it is activated only operate the unit after correcting the wiring Power supply wires must be attached securely If the power supply has a missing or wrong N phase equipment will break down Make sure that all wiring is secure the specified wires are used ...

Страница 16: ...ring sheathed cable 16 V 1 Electric wiring diagram Printed on the back of the electric box lid 2 Power wiring and ground wiring between outdoor units inside conduit When the wiring is routed out through the lateral panel 3 Transmission wiring 4 Pipe opening 5 Conduit 6 Power wiring and ground wiring 7 Cut off the shaded zones before use 8 Through cover 1 Knockout hole 2 Burr 3 If there are any pos...

Страница 17: ... from the indoor units must be connected to the F1 F2 In Out terminals on the PC board in the outdoor unit After installing the interconnecting wires inside the unit wrap them along with the on site refrigerant pipes using finishing tape as shown in figure 12 For the above wiring always use vinyl cords with 0 75 to 1 25 mm2 sheath or cables 2 core wires 3 core wire cables are allowable for the coo...

Страница 18: ...r etc Precautions when laying power wiring Do not connect wiring of different thicknesses to the power terminal block Slack in the power wiring may cause abnormal heat When connecting wiring which is the same thickness do as shown in the figure below For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on the terminal board Use an approp...

Страница 19: ...and field piping has been completed Refrigerant may only be charged after performing the leak test and the vacuum drying The refrigerant charge of the system must be less than 100 kg This means that in case the calculated refrigerant charge is equal to or more than 95 kg you must divide your multiple outdoor system into smaller independent systems each containing less than 95 kg refrigerant charge...

Страница 20: ...enance after installation of the unit BS2 SET BS2 SET BS3 RETURN BS1 MODE When charging a system charging over the permissible quantity can cause liquid hammer Always use protective gloves and protect your eyes when charging refrigerant When the refrigerant charging procedure is done or when pausing close the valve of the refrigerant tank immediately If the tank is left with the valve open the amo...

Страница 21: ...ect the cooling mode or heating mode for charging Continue with the automatic charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for charging in heating mode 7 Ready Press the button once within 5 minutes If the button is not pushed within 5 minutes P2 will be displayed on the remote controller Refer to 4 Remote controller malfunction c...

Страница 22: ...he remote controller When the charging amount is little the PE code may not be displayed but instead the P9 code will be displayed immediately If it is not as shown above correct the malfunction as indicated in the display of the remote controller and restart the complete charging procedure 10 Press the button to perform the temperature range check Out of range In these cases press the button once...

Страница 23: ...lly charging in cooling mode OR in heating mode Charging in heating mode 6 Start up Wait while the unit is preparing for charging in heating mode 7 Ready Press the button once within 5 minutes If the button is not pushed within 5 minutes P2 will be displayed on the remote controller Refer to 4 Remote controller malfunction code display on page 21 8 Operation When the following led display is shown...

Страница 24: ...ler malfunction code display on page 21 H1P H2P H3P H4P H5P H6P H7P w c c w w w w BS4 TEST BS4 TEST BS1 MODE LED display Default status before delivery Micro computer operation monitor Mode Ready Error Cooling Heating changeover Low noise Demand Multi Indivi dual Bulk master Bulk slave HAP H1P H2P H3P H4P H5P H6P H7P H8P Single outdoor unit system c x x w x x x x x Multiple outdoor unit system Mas...

Страница 25: ...rant charging from Start of automatic charging refrigerant as explained page 18 again 11 5 Checks after adding refrigerant Are the stop valves for both liquid and gas open Is the amount of refrigerant that has been added recorded 12 BEFORE OPERATION 12 1 Service precautions Pay attention to the fan It is dangerous to inspect the unit while the fan is running Be sure to turn off the main switch and...

Страница 26: ...parts Make sure to re attach the inspection cover 1 into the switch box cover 2 after the job is finished Location of the dip switches leds and buttons Led state Throughout the manual the state of the leds is indicated as follows Setting the dip switches only in case of a heat pump unit Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB...

Страница 27: ...x x Multiple outdoor unit system Master unit a a The state of the H8P multi LED in a multi system shows wich unit is the master unit w slave 1 unit c or slave 2 unit x Only the master unit is connected to the indoor units with interunit wiring c x x w x x x x w Slave unit 1 a c x x x x x x x c Slave unit 2 a c x x x x x x x x NOTE If you get confused in the middle of the setting process push the b...

Страница 28: ...al refrigerant state Perform the test operation as decribed in the paragraph Test operation procedure on page 26 In case refrigerant was added without using the leak detection function charging in cooling mode In the check operation the following checks and judgement will be performed Check of the stop valve opening Check for wrong wiring Judgement of piping length It takes 30 minutes to complete ...

Страница 29: ...the unit operation from a remote controller To abort the operation press the button The unit will stop after 30 seconds 6 Close the front panel in order to let it not be the cause of misjudgement 7 Check the test operation results by the led display on the outdoor unit 8 When the test operation is fully completed normal operation will be possible after 5 minutes Otherwise refer to Correcting after...

Страница 30: ...system uses R410A as refrigerant R410A itself is an entirely safe non toxic non combustible refrigerant Nevertheless care must be taken to ensure that air conditioning facilities are installed in a room which is sufficiently large This assures that the maximum concentration level of refrigerant gas is not exceeded in the unlikely event of major leak in the system and this in accordance to the loca...

Страница 31: ... in a concentration in excess of the maximum concentration level then it will be necessary to revise the system Please consult your supplier 15 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation NOTES A Where there are no smaller room divisions B Where there is a room division ...

Страница 32: ... 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 27 13 6 9 8 1 2 4 3 5 14 15 16 12 11 10 10 7 28 13 14 3 5 4 2 1 7 8 9 6 10 10 11 10 2 2 12 9 9 29 13 14 3 5 4 2 1 7 8 9 6 10 10 11 12 26 27 28 29 ...

Страница 33: ...4PW28163 1 ...

Отзывы: