background image

U-5~48MX3
Urban Multi air conditioner
4PW16235-1C

Installation manual

9

6.4.

Leak test and vacuum drying

The units were checked for leaks by the manufacturer.

Confirm that the valves are firmly closed before pressure test or
vacuuming.

Air tight test and vacuum drying

Air tight test: Make sure to use nitrogen gas. (For the service
port location, refer to the “Caution” label attached on the front
panel of the outdoor unit.) 

(See figure 19)

Pressurize the liquid and gas pipes (and oil equalizing pipe in case of
U-18~48MX3 type) to 3.8 MPa (38 bar) (do not pressurize more than
3.8 MPa (38 bar)). If the pressure does not drop within 24 hours, the
system passes the test. If the pressure drops, check where the
nitrogen leaks from.

Vacuum drying: Use a vacuum pump which can evacuate to
–100.7 kPa (5 Torr, –755 mm Hg)

1.

Evacuate the system from the liquid and gas pipes (and oil
equalizing pipe in case of U-18~48MX3 type) by using a vacuum
pump for more than 2 hours and bring the system to –100.7 kPa.
After keeping the system under that condition for more than 1 hour,
check if the vacuum gauge rises or not. If it rises, the system may
either contain moisture inside or have leaks.

2.

Following should be executed if there is a possibility of moisture
remaining inside the pipe (if piping work is carried out during the
raining season or over a long period of time, rainwater may enter the
pipe during work).

After evacuating the system for 2 hours, pressurize the system to
0.05 MPa (vacuum break) with nitrogen gas and evacuate the
system again using the vacuum pump for 1 hour to –100.7 kPa
(vacuum drying). If the system cannot be evacuated to –100.7 kPa
within 2 hours, repeat the operation of vacuum break and vacuum
drying.

Then, after leaving the system in vacuum for 1 hour, confirm that the
vacuum gauge does not rise.

Stop valve operation procedure

Introduction

Confirm the sizes of the stop valves connected to the system
referring to the table below.

Opening stop valve

1.

Remove the cap and turn the valve counterclockwise with the
hexagon wrench.

2.

Turn it until the shaft stops.

Do not apply excessive force to the stop valve. Doing so may break
the valve body, as the valve is not a backseat type. Always use the
special tool.

3.

Make sure to tighten the cap securely.

Closing stop valve

1.

Remove the cap and turn the valve clockwise with the hexagon
wrench.

2.

Securely tighten the valve until the shaft contacts the main body
seal.

3.

Make sure to tighten the cap securely.

For the tightening torque, refer to the table below.

(See figure 23)

<CAUTION>

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks are
present.

FLARE SHAPE and FLARENUT TIGHTENING TORQUE

Precautions when connecting pipes

See the following table for flare part machining dimensions.

When connecting the flare nuts, apply refrigerant oil to the inside
and outside of the flares and turn them three or four times at first.
(Use ester oil or ether oil.)

When loosening a flare nut, always use two wrenches in
combination. When connecting the piping, always use a spanner
and torque wrench in combination to tighten the flare nut.

See the following table for tightening torque.
(Applying too much torque may cause the flares to crack.)

After all the piping has been connected, use nitrogen to perform
a gas leak check.

1

Electric box lid

2

Service precautions
Label location

3

Caution
Label location

NOTE

Make sure to perform airtightness test and vacuum
drying using the service ports of the stop valve shown
in the table below.

U-5~16MX3

Liquid line stop valve
Gas line stop valve

U-18~48MX3

Liquid line stop valve
Gas line stop valve
Oil-equalizing line stop valve

U-5MX3 

U-8MX3 

 

U-10MX3

 

U-12MX3

U-14MX3

U-16MX3

Liquid line stop 

valve

Ø9.5

Ø12.7

Gas line stop valve

Ø15.9

Ø22.2

(*)

(*)

The model U-8MX3 supports on-site piping of Ø19.1 by the accessory pipes.

Ø25.4

(†)

(†) The model U-12~16MX3 supports on-site piping of Ø28.6 by the accessory 

pipes.

Tightening torque N•m (Turn clockwise to close)

Stop 

valve 

size

Shaft (valve body)

Cap 

(valve lid)

Service 

port

Flare nut

Gas line 

piping 

attached 

to unit

Ø6.4

5.4~6.6

Hexagonal 

wrench 

4 mm

13.5~16.5

11.5~13.9

14~17

Ø9.5

33~39

Ø12.7

8.1~9.9

18~22

50~60

Ø15.9

13.5~16.5

Hexagonal 

wrench 

6 mm

23~27

62~75

Ø22.2

27~33

Hexagonal 

wrench 

10 mm

36~44

22~28

Ø25.4

1

Service port

2

Cap

3

Hexagon hole

4

Shaft

5

Seal

Pipe size

Tightening 

Torque (N•m)

A (mm)

Flare shape

Ø9.5

32.7~39.9

12.8~13.2

Ø12.7

49.5~60.3

16.2~16.6

Ø15.9

61.8~75.4

19.3~19.7

1 2 3

4

1

Piping union

2

Spanner

3

Flare nut

4

Torque wrench

R=0.4~0.8

45  ±2

90 ±2

A

Содержание U-10MX3XPA

Страница 1: ...U 14MX3XPQ A U 16MX3XPQ A U 18MX3XPQ U 20MX3XPQ U 22MX3XPQ U 24MX3XPQ U 26MX3XPQ U 28MX3XPQ U 30MX3XPQ U 32MX3XPQ U 34MX3XPQ U 36MX3XPQ U 38MX3XPQ U 40MX3XPQ U 42MX3XPQ U 44MX3XPQ U 46MX3XPQ U 48MX3XPQ INSTALLATION MANUAL URBAN MULTI AIR CONDITIONER ...

Страница 2: ... D c H h h1 h2 1500 1 3 5 4 2 2 mm 6 3 1 0 0 0 1 0 0 0 1000 1 50 0 1500 1500 722 737 80 80 765 A B 1 2 4 5 6 7 3 7 1 6 1 2 4 5 3 5 3 3 2 1 5 3 3 1 3 3 4 4 4 4 9 4 4 5 7 7 5 5 2 5 5 5 5 6 2 6 9 2 2 6 6 8 2 2 1 1 2 2 2 1 2 2 5 1 A B A B 4 2 3 1 1 2 3 4 5 6 7 U 5MX3 U 8 10MX3 U 12 16MX3 U 5 16MX3 U 18 48MX3 ...

Страница 3: ... 4 5 6 7 17 8 12 20 18 18 1 2 1 2 5 3 3 3 3 5 5 5 7 5 4 4 4 4 4 6 A B F2 F2 F1 F1 A B C Q1Q2 1 4 3 2 2 6 6 6 5 1 2 3 3 4 4 5 6 3 4 3 4 6 3 4 6 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 2 1 A B C A B C F1 F2 F1 F2 Q1 Q2 A B C F1 F1 F2 F2 Q1 Q2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 6 1 2 7 C H SELECTOR TO IN D UNIT TO OUT D UNIT TO MULTI UNIT A1P 3 8 9 11 10 12 14 13 15 U 5 16MX3 U 18 48MX3 ...

Страница 4: ... 16 17 18 5 1 7 10 3 2 9 6 6 6 6 7 4 11 8 6 6 6 6 6 6 7 7 9 8 4 11 6 6 1 10 3 2 6 6 6 6 18 TO IN D UNIT F1 F2 DS1 1 2 3 4 OFF ON O U T I N F1 F2 F1 F2 F1 F2 1 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N 1 2 3 4 5 4 16 17 18 19 20 21 22 23 U 5 10MX3 U 12 16MX3 U 12 16MX3 U 5 10MX3 ...

Страница 5: ...10A refer to the product catalogs Total capacity quantity of indoor units U 5 48MX3 Urban Multi air conditioner Installation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE UNIT DO NOT THROW IT AWAY KEEP IT IN YOUR FILES FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQUIPMENT OR ACCESSORIES COULD RESULT IN ELECTRIC SHOCK SHORT CIRCUIT LEAKS FIRE OR OTHER DAMAGE TO THE EQUI...

Страница 6: ...efer to figure 1 and choose one of the possibilities In case of an installation site where only the sides A B have obstacles the wall heights have no influence on any indicated service space dimensions 3 There is no danger of fire due to leakage of inflammable gas 4 Ensure that water cannot cause any damage to the location in case it drips out the unit e g in case of a blocked drain pipe 5 The pip...

Страница 7: ...quipment personal computers etc See figure 2 In extreme circumstances you should keep distances of 3 m or more and use conduit tubes for power and transmission lines In heavy snowfall areas select an installation site where snow will not affect operation of the unit The refrigerant R 410A itself is nontoxic nonflammable and is safe If the refrigerant should leak however its concentration may excee...

Страница 8: ...igerant All field piping must be installed by a licensed refrigeration technician and must comply with relevant local and national regulations CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing copper to copper refrigerant piping Particularly for the HFC refrigerant piping Therefore use the phosphor copper brazing filler metal BCuP which does not require flux Flux has...

Страница 9: ...ed pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Cautions for installation of multiple outdoor units 1 The piping between the outdoor units must be routed level or slightly upward to avoid the risk of oil detention into the piping side Pattern 1 Pattern 2 Prohibited pattern Change to Pattern 1 or 2 Be sure to use the supplied accessory...

Страница 10: ...he outdoor unit connecting pipe kits or between the outdoor units exceeds 2 m create a rise of 200 mm or more in the gas line within a length of 2 m from the kit If 2 m If 2 m A Unit A B Unit B C Unit C X Not allowed O Allowed 1 To indoor unit 2 Oil collects to the stopping outdoor unit 3 Oil collects to the outdoor unit C when the system stops A B B A 1 1 2 2 2 2 2 2 1 1 A B C C A B 3 3 1 1 200 m...

Страница 11: ...it 8 i 40 m Refrigerant branch kit selection Refrigerant branch kits can only be used with R 410A How to select the line branch pipe When using line branch pipe at the first branch counted from the outdoor unit side Choose from the following table in accordance with the capacity of the outdoor unit For line branch pipes other than the first branch select the proper branch kit model based on the to...

Страница 12: ...piping lengths are as below R 30x0 25 10x0 17 10x0 11 40x0 054 49x0 022 6 7 538 R 7 5 kg A B C D Outdoor unit capacity type Piping size outer diameter Gas pipe Liquid pipe U 5MX3 Ø15 9 Ø9 5 U 8MX3 Ø19 1 U 10MX3 Ø22 2 U 12 16MX3 Ø28 6 Ø12 7 U 18 22MX3 Ø15 9 U 24MX3 Ø34 9 U 26 34MX3 Ø19 1 U 36 48MX3 Ø41 3 Indoor capacity index Piping size outer diameter Gas pipe Liquid pipe 200 Ø15 9 Ø9 5 200 x 290 ...

Страница 13: ...at type Always use the special tool 3 Make sure to tighten the cap securely Closing stop valve 1 Remove the cap and turn the valve clockwise with the hexagon wrench 2 Securely tighten the valve until the shaft contacts the main body seal 3 Make sure to tighten the cap securely For the tightening torque refer to the table below See figure 23 CAUTION Always use a charge hose for service port connect...

Страница 14: ... additional refrigerant to be charged on page 8 and fill in the amount in the Additional refrigerant charge label attached to the unit After the vacuum drying is finished charge the additional refrigerant in its liquid state through the liquid stop valve service port taking into account following instructions Check that gas and liquid stop valves are closed Stop the compressor and charge the speci...

Страница 15: ...door unit installed See figure 9 1 Fully open the gas line stop valve oil equalizing line stop valve liquid line stop valve and valves A and B above must be left fully closed start the additional refrigerant charge operation 2 After the system is charged with a specified amount of refrigerant press the confirmation button BS3 on the P board A1P in the outdoor unit to stop the additional refrigeran...

Страница 16: ...nection wiring to outdoor outdoor transmission F1 F2 outdoor indoor transmission F1 F2 outdoor multi transmission Q1 Q2 refer to 7 5 Examples on page 13 For connection wiring to the central remote controller refer to the installation manual of the central remote controller Use insulated wire for the power cord Phase and frequency Voltage Recommended fuses Transmission line section U 5MX3 3N 50 Hz ...

Страница 17: ...an earth leak detector capable of handling high harmonics needs to be used in order to prevent malfunctioning of the earth leak detector itself Earth leak detector which are especially for protecting ground faults should be used in conjunction with main switch or fuse for use with wiring This unit has a negative phase protection circuit If it operates only operate the unit after correcting the wir...

Страница 18: ... torque for the terminal screws Precautions when connecting the ground When pulling the ground wire out wire it so that it comes through the cut out section of the cup washer An improper ground connection may prevent a good ground from being achieved 1 Cool heat selector 2 Outdoor unit PC board A1P 3 Take care of the polarity 4 Use the conductor of sheathed wire 2 wire no polarity 5 Terminal board...

Страница 19: ...d The interconnecting wiring between the outdoor units must be 30 m See the paragraph Fixing field line connection on page 14 A Electric wiring diagram Printed on the back of the electric box lid 1 Cut off the shaded zones before use 2 Through cover 3 Power wiring between outdoor units When the wiring is routed out through the lateral panel 4 Set apart 5 Transmission wire 6 Knockout hole 7 Power w...

Страница 20: ...ly For that purpose perform normal operation using the remote controller after the check operation Make sure that the circuit breaker on the power supply panel of the installation is switched off Attach the power wire securely Introducing power with a missing N phase or with a mistaken N phase will break the equipment After completing installation be sure to open the valve Operating the unit with ...

Страница 21: ...centration level is required According to the appropriate European Standard the maximum allowed concentration level of refrigerant to a humanly space for R 410A is limited to 0 44 kg m3 Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than air Installation error Malfunction code Remedial action The stop valve of an outdoor unit is left...

Страница 22: ... of the maximum concentration level then it will be necessary to revise the system Please consult your supplier NOTES amount of refrigerant in a single unit system amount of refrigerant with which the system is charged before leaving the factory additional charging amount amount of refrigerant added locally in accordance with the length or diameter of the refrigerant piping total amount of refrige...

Страница 23: ...NOTES NOTES ...

Страница 24: ...4PWEN16235 1C ...

Отзывы: