5-2 Receiver Troubleshooting
<Indicators on emitter>
Upper application indicator: Lights red
Lower application indicator: Lights red
Digital indicator
(Turns OFF or blinking yellow number)
Stable light reception indicator
Frequency indicator
Function setting indicator
OSSD indicator
(Turns OFF or lights red)
Upper application indicator
(Turns OFF or lights blue)
Lower application indicator
(Turns OFF or lights blue)
Interlock indicator
(Turns OFF or lights yellow)
<All indicators are turns OFF>
Cause
Remedy
Power is not supplied.
Make sure the power supply capacity is sufficient.
Connect the power supply correctly.
Supply voltage is outside the specified range.
Set the supply voltage correctly.
Connector not firmly connected.
Connect the connector firmly.