• VRF Systems • Indoor Units
4
• Indoor Units • FREE AIR CASSETTE • S-UM4JPQ
1
Specifications
13
1
1-2 ELECTRICAL SPECIFICATIONS
S-20UM4JPQ
S-25UM4JPQ
S-32UM4JPQ
S-40UM4JPQ
S-50UM4JPQ
Power Supply
Name
J
Frequency
Hz
50/60
Voltage
V
220-240/220
Current
Minimum circuit amps
(MCA)
A
0.4
0.4
0.4
0.5
0.6
Maximum fuse amps (MFA) A
16
16
16
16
16
Full load amps (FLA)
A
0.3
0.3
0.3
0.4
0.5
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA <= 4 x FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker
1-2 ELECTRICAL SPECIFICATIONS
S-63UM4JPQ
S-80UM4JPQ
S-100UM4JPQ
S-125UM4JPQ
Power Supply
Name
J
Frequency
Hz
50/60
Voltage
V
220-240/220
Current
Minimum circuit amps
(MCA)
A
0.9
0.9
1.4
1.9
Maximum fuse amps (MFA) A
16
16
16
16
Full load amps (FLA)
A
0.7
0.7
1.1
1.5
Voltage range
Minimum
V
-10%
Maximum
V
+10%
Notes
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below
or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA <= 4 x FLA
next lower standard fuse rating minimum 16A
select wire size based on the MCA
instead of a fuse, use a circuit breaker