11.11.4 SETTINGS
CONTROL USING TWO REMOTE CONTROLLERS
•
If both the infrared remote controller and the optional wired remote controller are being used together, either
remote controller can be used to operate the indoor units. (The indoor unit can be used to operated with the last
switch pressed having priority.)
•
Up to 2 optional wired remote controllers can be connected and used.
1 REMOTE CONTROLLER GROUP CONTROL
•
When using group control, up to a maximum of 16 indoor units can be connected. (Do not mix heat pump units
and cooling only units.)
•
For details on how to set the address (A/C No.) for group control, refer to the “Setting for 1 remote controller
group control” section in the installation instructions provided with the indoor unit.
Wired
control
(optional)
Indoor unit No. 1
Indoor unit No. 2
Indoor unit No. 3
DIP
switch
DIP
switch
DIP
switch
Printed
circuit
board
Printed
circuit
board
Printed
circuit
board
Terminal
block
Terminal
block
Terminal
block
Infrared receiver
LOCAL SETTING
•
Press the SET switch
○
2 to operate the “Local setting mode”.
•
Use
the switches TEMP to choose the “Mode No.”
•
Use
the switches TIMER to choose the “Setting value”.
•
Press the SET switch
○
1 to check the setting details.
The setting details are displayed for approximately 4 seconds and then
it exits the local setting mode.
If no operation is performed, the “Local setting mode” clears after 30 seconds.
Model No.
Item
Setting Value
Setting Remarks
000 Clear
address
00
Indoor unit address setting
001 ~ 200
Set address
“001” to “200”
000
Not set (Clear)
001
Low sound level 1
002
Low sound level 2
02
Low sound at night
003
Low sound level 3
000 Clear
address
06
Outdoor unit address setting
001 ~ 199
Set address
“001” to “199”
Note: 1. The default setting at shipment is “000”.
SETTING INDOOR UNIT ADDRESS
•
Setting and clearing the indoor unit address (Central control address) can be performed.
•
It is possible to set the address value from “001” to “200”. Setting the address to “000” clears it.
•
Set the mode number to “00” and choose a setting value from “000” to “200” according to the local setting
procedure.
Содержание S-32NA1E5
Страница 4: ...4 23 6 Heating 430 24 Exploded View and Replacement Parts List451 24 1 Indoor Unit 451 ...
Страница 12: ...12 ...
Страница 40: ...40 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5 ...
Страница 41: ...41 4 2 60 x 60 Cassette Type Indoor Unit 4 2 1 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5 ...
Страница 42: ...42 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5 ...
Страница 43: ...43 4 4 Slim Hide Away Type Indoor Unit 4 4 1 S 22NA1E5 S 28NA1E5 S 32NA1E5 S 36NA1E5 S 45NA1E5 S 56NA1E5 ...
Страница 44: ...44 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5 ...
Страница 45: ...45 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5 ...
Страница 51: ...51 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Страница 52: ...52 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Страница 53: ...53 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Страница 54: ...54 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Страница 55: ...55 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Страница 56: ...56 7 6 Outdoor Unit LA1E5 Series ...
Страница 57: ...57 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series ...
Страница 58: ...58 ...
Страница 59: ...59 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series ...
Страница 60: ...60 ...
Страница 61: ...61 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series ...
Страница 62: ...62 ...
Страница 63: ...63 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series ...
Страница 64: ...64 ...
Страница 65: ...65 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series ...
Страница 66: ...66 ...
Страница 67: ...67 8 6 Outdoor Unit LA1E5 Series ...
Страница 68: ...68 ...
Страница 70: ...70 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE ...
Страница 74: ...74 9 6 Outdoor Unit LA1E5 Series 9 6 1 Main PCB ...
Страница 75: ...75 9 6 2 Noise Filter PCB CN TH1 CN OPT4 CN OPT3 CN V1 CN V2 CN OPT1 CN PWR CN OPT2 CN RY1 CN HOT ...
Страница 76: ...76 9 6 3 Capacitor PCB DCN IN DCN OUT DCP IN DCP OUT ...
Страница 195: ...195 ...
Страница 201: ...201 ...