![Panasonic S-100PN1E5A Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/panasonic/s-100pn1e5a/s-100pn1e5a_installation-instructions-manual_269822007.webp)
7
ENGLISH
БЪ
ЛГ
АР
СКИ
E
ΛΛΗΝΙΚΆ
PORTUGUÊS
РУССКИЙ
УКР
АЇНСЬКА
3. SELECTING THE LOCATION FOR THE INDOOR UNIT
3-1.
Required Minimum Space for Installation and Service.
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfied and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
Fig.3-1
POSITION OF SUPENSION BOLT
Apply a joint-canvas between the unit and duct to absorb unnecessary
vibration.
Install the unit leaning to a drainage hole side as a figure for easy water
drainage.
Top view
(Unit:mm)
Inspection hole
Control box
(600 x 600)
600
<Front>
1000
600
Front view
Above 250cm
A
B
C
E
D
1~3mm
Absorber
Drainage hole
Caution
Remove the absorber at air return
hole before installation.
TYPE
A
B
C
D
E
S-36PN1E5A
840 780 523
64
650
S-45PN1E5A
S-50PN1E5A
S-60PN1E5A
1060 1000 523
64
650
S-71PN1E5A
S-100PN1E5A
1260 1200 523
64
650
S-125PN1E5A
S-140PN1E5A
(Unit:mm)
Fig.3-1.1
P07-T11630.indb 7
2/27/2012 9:20:57 AM
Содержание S-100PN1E5A
Страница 1: ......