50
Electrical Wiring
5.2 Recommended wire lengths and diameters
Important
● The letter coding (A to F) used in the following tables refers to the wiring system
diagrams in the next section.
● For information on “(A) Power supply of outdoor unit” refer to the “Installation
Instructions“ for the relevant outdoor unit.
Indoor unit
Type
(B) Power supply
Time delay fuse or circuit breaker
AHU Kit
2.5 mm
2
(AWG#13)
10 – 16 A
Max. 150 m
Control wiring
(C) Inter-unit control wiring
(between outdoor and indoor units
(D) Remote
control wiring
(E) Control wiring
for group control
1
(F) Inter-outdoor-
unit control wiring
1
0.75 mm
2
(AWG# 18)
Use shielded wiring*
or
2.0 mm
2
(AWG# 14)
Use shielded wiring*
0.75 mm
2
(AWG# 18)
Use shielded wiring*
0.75 mm
2
(AWG# 18)
Use shielded wiring*
0.75 mm
2
(AWG# 18)
Use shielded wiring*
Max. 1,000 m
Max. 2,000 m
Max. 500 m
Max. 200 m (total)
Max. 300 m
1 “E” and “F” are relevant for ECOi multi connection systems only.
i