102
AHU Kit – Installation Instructions –
11/2021
Control
7
7.2.2 Operation
Status messages
After the thermostat has been switched on, the PV and SV displays jointly show a set sequence of
three status messages before they change to the normal view where the current process value is
shown on the PV display and the currently set temperature value is shown on the SV display.
PV
SV
SV
PV
SV
PV
UEr
Control voltage switched on
Normal view
4.
The
two
displays
finally
change
to
normal
view:
PV = currently measured temperature (process value)
SV = currently set temperature value
1.
Software version view (factory setting)
2.
Input
specification
view
(factory
setting)
3.
Measuring range (factory setting)
PV = lower limit
SV = upper limit
Changing the set temperature value
To change the set temperature value, perform the following steps:
1. During operation, press the
SSEETT
button.
TR-16e
SSEETT
1
x
briefly
The SV display is blinking.
2. Change the set value as required, using the
,
and
buttons.
TR-16e
SSEETT
The SV display shows the desired temperature value.
3.
Confirm the setting by pressing the
SSEETT
button.
TR-16e
SSEETT
1
x
briefly
The SV display permanently shows the new set value.
Important
The set temperature value, which is adjustable by the above procedure, can be used in different
ways and with different functions depending on how the thermostat is used in the individual
application.
7.2.3 Initial Settings, p. 107
.