Note
The surge protector for an extension is different from that for trunks.
Installation of an Earth Rod
Trunk
PBX
Earth Rod
(Underground)
Surge Protector
Earthing
Wire
1.
Connect the earth rod to the surge protector using an earthing wire with a cross-sectional area of at
least 1.3 mm
2
.
2.
Bury the earth rod near the protector. The earthing wire should be as short as possible.
3.
The earthing wire should run straight to the earth rod. Do not run the wire around other objects.
4.
Bury the earth rod at least 50 cm (20 in) underground.
Note
•
The above figures are recommendations only.
•
The length of earth rod and the required depth depend on the composition of the soil.
3.2.10 Backup Battery Connection
The backup battery and Back-up Battery Cable provide a backup power supply to allow full use of the PBX
in the event of a power failure. In case of power failure, the backup battery automatically maintains the pow-
er to the PBX without interruption.
User-supplied Items
•
Backup Battery: VRLA (Valve Regulated Lead Acid) 12 V DC × 1
•
Back-up Battery Cable: KX-A227
WARNING
•
There is a danger of explosion if a backup battery is incorrectly replaced. Replace only with the
same or equivalent type recommended by the battery manufacturer. Dispose of used batteries ac-
cording to the manufacturer’s instructions.
•
Make sure that you do not short the backup battery or cables.
CAUTION
•
Make sure that the Back-up Battery Cable is securely fastened to both the backup battery and the
PBX.
•
Make sure that the polarities of the backup battery and wiring are correct.
•
Use the correct type of Back-up Battery Cable for the PSU.
3.2.10 Backup Battery Connection
58
Содержание KX-HTS824
Страница 3: ... P SIP Panasonic SIP Phones KX HDV series System Components 3 ...
Страница 22: ...1 5 F C C REQUIREMENTS AND RELEVANT INFORMATION 22 ...
Страница 36: ...2 3 3 System Capacity 36 ...
Страница 93: ...Section 5 Maintenance This section describes maintenance procedures 93 ...
Страница 97: ...Section 6 Troubleshooting This section provides information on the PBX and tele phone troubleshooting 97 ...
Страница 103: ...Section 7 Appendix This section provides information about System Prompt Languages and the revision history 103 ...