background image

KC2S(AKC2)/KE2S(AKE2)

PRODUCT TYPES

1. KC2S Eco-COUNT METER

Notes: 1. Eco-COUNT METER (AKC2421/AKC2621) is a product package consisting of the main unit, a dedicated current transformer (CT), and trunk cable.

2. Only the installation frame installation type includes rubber gasket and installation frame.
3. The maximum allowable current of the intermediate power cable is 15 A.

2. KE2S Eco-HOUR METER

Notes: 1. Eco-HOUR METER (AKE2421/AKE2621) is a product package consisting of the main unit, an exclusive use current transformer (CT), and trunk cable.

2. Only the installation frame type includes rubber gasket and installation frame.
3. The maximum allowable current of the intermediate power cable is 15 A.

SPECIFICATIONS

POWER-ON COUNTER 

POWER-ON HOUR METER

KC2S Eco-COUNT METER
KE2S Eco-HOUR METER

Product Name

Installation type

Front reset

Measurement count range

Part No.

Eco-COUNT METER main unit*

1

Installation frame type*

2

Available

0 to 99999999

AKC2421

One-touch installation type

AKC2621

Intermediate power cable*

3

AKE2811

Product Name

Installation type

Front reset

Measurement time range

Part No.

Eco-HOUR METER main unit*

1

Installation frame type*

2

Available

0 to 99999.9h

AKE2421

One-touch installation type

AKE2621

Intermediate power cable*

3

AKE2811

Eco-COUNT METER and Eco-HOUR METER are ideal for maintenance 
of your facilities and machinery.

FEATURES

1. Easy to install on existing machinery

Just attach the dedicated CT to your existing 
cables. There is no need to install any 
additional cabling.

2. Built-in battery

The built-in battery allows the units to be 
installed anywhere.

3. Economically priced
4. Compact size doesn’t take up space 
(DIN 24 x 48)

Easy to install even in cramped spaces.

5. Two installation methods available 
(Separate models)

Two installation methods are available: The 
extremely easy-to-use one-touch installation, 
and the installation frame installation, used for 
timers/counters (protective construction IP66).
Select the installation type that suits the 
location.

6. Letter’s height is 8.7 mm

A large LCD panel is used, with a highly 
legible 8.7 mm letter’s height.

7. Conform to CE marking (EMC directive)

Eco-COUNT METER

Eco-HOUR METER

Dedicated CT

Item

Specifications

Product name

Eco-COUNT METER (Power-on Counter)

Eco-HOUR METER (Power-on Hour Meter)

Part No.

AKC2421/AKC2621

AKE2421/AKE2621

No. of digits

8 digits

6 digits

External power supply

Not required (built-in battery)

Counting max. speed

2Hz (CT through current minimum power-up time: 250ms, ON:OFF =1:1)

Time accuracy

±

100ppm (25

°

C)

Measurement range

0 to 99999999 counts

0 to 99999.9h

Detection sensitivity (through current)

Counting start: 0.5A to 80A (50/60Hz)*

1

Timing start: 0.5A to 80A (50/60Hz)*

1

Counting stop: 0.2A (50/60Hz) or less

Timing stop: 0.2A (50/60Hz) or less

Reset input

Min. input signal width

100ms

Input method (signal)

• Non voltage input using contacts or open collector connection

• Input impedance, When shorted: Max.10k

Ω

, When open: Min.750k

Ω

• Residual voltage: Max. 0.5V

Display method

7-segment LCD

Breakdown voltage (initial)

Between live and dead metal parts: 1,000V AC for 1 minute.

Insulation resistance (initial)

Between live and dead metal parts: Min. 100M

Ω

 (measured at 500 V DC)

Protective construction*

2

IEC Standard IP66 (only front panel with rubber gasket)

Vibration resistance (Functional)

10 to 55 Hz: 1 cycle/min., signal amplitude of 0.15mm 

.006inch

 (10 min. on 3 axes)

Vibration resistance (Destructive)

10 to 55 Hz: 1 cycle/min., signal amplitude of 0.375mm 

.015inch

 (1 hr. on 3 axes)

Shock resistance (Functional)

Min. 98m 

321.522ft

/s

2

  (4 times on 3 axes)

Shock resistance (Destructive)

Min. 294m 

964.567ft

/s

2

 (5 times on 3 axes)

Operating temperature

–10 to +50

°

+14 to +122

°

F

 (without frost or dew)

Storage temperature

–25 to +65

°

–13 to +149

°

F

 (without frost or dew)

Ambient humidity

35 to 85% RH (at 20

°

C non-condensing)

Battery life*

3

7 years (at 25

°

77

°

F

)

10 years (at 25

°

77

°

F

)

Mass (weight)

Approx. 110g (Dedicated CT included)

Approx. 105g (Dedicated CT included)

Notes: 1. Maximum cable diameter is 10 mm.

2. See page 13, “NOTES 4. Waterproofing Construction” for details about the protective 

construction (IP66).

3. Battery life is calculated based on the above conditions.

This is not a guarantee of actual battery life.
Please use this as a guide for replacing the battery only.
The actual battery life may be shortened, depending on the utilization environment of 
the main unit.

!LL2IGHTS2ESERVEDÚ#

OPYRIGHT

0ANASONIC%LECTRIC7ORKS#O,TD

Compliance with RoHS Directive

26/03/2013

Содержание KC2S Eco-COUNT METER

Страница 1: ...MC directive Eco COUNT METER Eco HOUR METER Dedicated CT Item Specifications Product name Eco COUNT METER Power on Counter Eco HOUR METER Power on Hour Meter Part No AKC2421 AKC2621 AKE2421 AKE2621 No of digits 8 digits 6 digits External power supply Not required built in battery Counting max speed 2Hz CT through current minimum power up time 250ms ON OFF 1 1 Time accuracy 100ppm 25 C Measurement r...

Страница 2: ...1 Class A EN55011 Group 1 Class A EN61000 4 2 4 kV contact EN61000 4 3 10 V m AM 80 MHz to 1 GHz EN61000 4 4 1 kV Signal line EN61000 4 6 10 V m AM 0 15 MHz to 80 MHz EN61000 4 8 30 A m 50Hz RESET h Eco HOUR METER KE2S Front reset key Lock switch Notes 1 Factory setting 2 Make the switch setting before installing to panel 3 Common to Eco COUNT METER and Eco HOUR METER Terminal block side LCD side ...

Страница 3: ...HOUR METER installed by one of the methods described above 3 Terminal layout and wiring diagrams Common to Eco COUNT METER and Eco HOUR METER Notes 1 Terminal 2 and 4 are connected inside 2 The CT does not have polarity 4 CT input 1 2 3 Reset input or Intermediate power cable AKE2811 200 10 7 874 394 Note We recommend using an intermediate power cable when attaching the dedicated CT to a non Y spl...

Страница 4: ...Take particular care of inter cable capacitance when using shielded cables 2 How to reset multiple panel installation type units all at once Notes 1 Use the following as a guide for choosing transistors used for input Tr Leakage current 1μΑ 2 Use as small a diode D as possible in the forward voltage so that the voltage between terminals 3 and 4 during reset input meets the standard value 0 5V At I...

Страница 5: ...ter replacing the battery return the battery cover 5 to the case Verify that the hook of the battery cover is properly engaged Before using press the reset key 6 on the front One touch installation type 1 Using a tool remove the up down hook of the case 1 Pull the unit 2 away from the case 2 Remove the battery 3 from the side of the unit Do not touch the display or other parts 3 Before inserting w...

Отзывы: