STANDARDS

 

VBHNxxxSJ and VBHNxxxKJ series comply with the 
requirements of IEC61215, IEC61730

-

1, IEC61730

-

and the CE mark.

 

APPLICATION CLASS OF PRODUCT

 

HIT

TM

 are applied to application 

class A

 and 

safety 

class II

. It may be applicated in systems operating at 

greater than 50 VDC or 240 W, where general contact 
access is anticipated. 

 

FIRE CLASS OF PRODUCT

 

The fire rating of this module is valid only when 
mounted in the manner specified in the mechanical 
mounting instructions.

 

HIT

TM

 fill 

fire class C 

that provides to IEC61730

-

2. 

Class C roof coverings are effective against light fire 
test exposures. Under such exposures, roof coverings 
of this class afford a light degree of fire protection to 
the roof deck, do not slip from position, and are not 
expected to produce flying brands.

 

JUNCTION BOX AND TERMINALS

 

• 

Modules equipped with one junction box 

contain terminals for both positive and nega-
tive polarity, and bypass diodes.

 

• 

One terminal is dedicated to each polarity (with 

the polarity symbols engraved onto the body of 
the junction box) (see Figure 2).

 

BYPASS DIODE

 

• 

When the modules in series strings are shaded 

partially, it may cause reverse voltage across 
cells or modules, because the current from 
other cells in the same series is forced to flow 
through the shaded area. This may cause unde-
sirable heating to occur.

 

• 

The use of a diode to bypass the shaded area 

can minimize both heating and array current 
reduction.

 

• 

All modules are equipped with factory installed 

bypass diodes. The factory installed diodes 
provide proper circuit protection for the sys-
tems within the specified system voltage, so 
that you do not need any other additional 
bypass diodes.

 

• 

Specifications of bypass diodes for the 

VBHNxxxSJ modules are as follows:

 

Number of bypass diode: 4 diodes

 

Number of series cells per bypass diode: 24 
cells / diode  (See Figure 3). 

 

MECHANICAL LOADING

 

The method offers a maximum load as shown in the 
table 

Mount location and load resistance

” 

in Figure 1 

and Figure 5 is a static state on the module surface.

 

 

 

 

 

 

 

 

 

 

Cable

 

Figure 2. Configuration of Junction 
Box

 

Connector (SMK 
plug)

 

Positive (+)

 

Negative (

-

)

 

24 cells / diode

 

24 cells / diode

 

24 cells / diode

 

24 cells / diode

 

Figure 3. Number of series cells per by-
pass diode

 

Содержание HIT VBHNxxxSJ53 series

Страница 1: ...mes listed in this manual are trademarks or registered trademarks of respective companies VBHNxxxSJ53 SJ54 KJ01 KJ02 series Photovoltaic Module HITTM Thank you for choosing Panasonic photovoltaic module HITTM Please read this manual completely before you install or use HITTM With proper operation and maintenance HITTM will provide you with clean renewable solar electricity for many years This manu...

Страница 2: ...s are connected in series pro ducing higher voltages The shock hazard increases as modules with nominal open circuit voltage Voc in excess of 45 V and or modules rated for maxi mum system voltage in excess of 45 V Wear suitable clothing gloves and guards to prevent from direct contact with 30 VDC or greater Work only in dry conditions with dry modules and dry tools Children and unauthorized person...

Страница 3: ...9 6 69 7 71 0 Short Circuit Voltage Isc 90 A 6 03 6 07 6 08 Maximum Power Voltage Vpm V 57 6 58 0 59 4 Maximum Power Current Ipm A 5 65 5 70 5 65 Temperature coefficient for Pmax 0 258 Temperature coefficient for Voc 0 235 Temperature coefficient for Isc 0 055 Cell Number in Series pcs 96 Cell Type Silicon hetero junction Maximum System Voltage Vsys V 1000 Maximum over current protection rating A ...

Страница 4: ...Dimensions in mm Side The positions of the holes are all symmetrical against the center of the module Front side Section A A Section B B Back side Mounting location range L1 0 230 230 L2 450 380 345 S1 0 S2 250 Load resistance Positive load 2400 Pa 5400 Pa 2400 Pa 5400 Pa Load resistance Negative load 2400 Pa 4400 Pa 2400 Pa 5400 Pa Module locations and load resistance Depending on internal standa...

Страница 5: ...graved onto the body of the junction box see Figure 2 BYPASS DIODE When the modules in series strings are shaded partially it may cause reverse voltage across cells or modules because the current from other cells in the same series is forced to flow through the shaded area This may cause unde sirable heating to occur The use of a diode to bypass the shaded area can minimize both heating and array ...

Страница 6: ...exposed to moisture shall not be employed alone or in combinations that could result in deterioration or corrosion Clearance of 10cm between the roof surface and module frame is required to allow cooling air to circulate around the back of the module This also allows any condensation or moisture to dissipate Install modules so that air can circulate between the roof and the module Do not contact a...

Страница 7: ...s that connect to ap propriate FUSE for each series string or each module For the installation of connection devices refer to the installation manual of connection devices Do not connect modules in parallel without maximum over current protection ARRAY WIRING The term array is used to describe the assem bly of several modules on a support structure with associated wiring When installing a PV array...

Страница 8: ...lt water 3 Heavy snow falls areas 4 Sand and dust damage is excessive at the installa tion place Heavy dirt areas by sand or dust e g desert a quarry etc 5 Installation in places where there is a concern about deterioration of modules such as heavy air pollution chemically active vapors acid rain and or soot ammonia gas etc UNPACKING AND HANDLING Do not hit the back sheet of a module by the connec...

Страница 9: ... caused by deter gents When cleaning the PV module please do not put detergent on the junction box or connector If detergents and chemical substances adhere the junction box and connectors may be deteri orated or damaged DISPOSAL OF OLD EQUIPMENT This symbol on the products and or accompanying documents means that used electrical and electronic products must not be mixed with general household was...

Страница 10: ...10 Edition Revision Date Revised Item Revised Content TENTATIVE 2017 12 15 TENTATIVE 2 2017 12 20 Appearance drawing Fig 1 Change of Appearance drawing REVISION HISTORY ...

Отзывы: