* The status of automatic address setting is displayed as follows.
Example:
(ready to start automatic address setting)
The meanings for the last digits displayed are as follows.
: Ready to start automatic address setting
: Waiting for indoor unit automatic address preparation
: Engine running
: Checking indoor units
: Setting addresses
: Setting completed
* To cancel automatic address setting with heating operation before it is completed, press and hold the SET key for 1
second.
The setting in progress indicator will turn off.
* If automatic address setting is not successful with heating operation, follow the procedure below to perform automatic
address setting with cooling operation.
<Automatic address setting with cooling operation>
(1) Turn on power to all systems.
(2) Select the
(initial settings) menu item to display
on the outdoor unit (with the smallest
).
address) in the refrigerant tubing system for which you want to set addresses.
(3) Use the UP and DOWN keys to select the automatic address setting with cooling operation (
(4) The remaining procedure is the same as steps (4) to (6) above.
* If automatic address setting is not successful with engine operation, refer to “Manual address setting” to set the
addresses.
<Manual address setting> Perform the following using the remote controller.
<<Setting the system addresses>>
(1) Press the ,
CANCEL
, and
SET
buttons simultaneously for at least 4 seconds to enter the advanced setting mode
and display “CODE No.
”.
(2) Press the
or
temperature adjustment buttons to display “CODE No.
” (system addresses).
(3) Press the
or
time adjustment buttons to change “SET DATA” to the desired system address.
à
à
…
can be displayed in “SET DATA”.
(4) Press the
SET
button to confirm the setting. (The display stops blinking and remains lit.)
<<Setting indoor unit addresses>>
or
temperature adjustment buttons to display “CODE No.
” (indoor unit addresses).
(5) Press the
(6) Press the
or
time adjustment buttons to change “SET DATA” to the desired indoor unit address.
à
à
…
can be displayed in “SET DATA”.
CAUTION:
Do not set the address to a value larger than the number of indoor units configured on the out
-
door unit (see Section 7). In addition, do not use the same address for units within a common
refrigerant system.
(7) Press the
SET
button to confirm the setting. (The display stops blinking and remains lit.)
(8) Finally, press the button to return the remote controller to standard mode.